| Plan Review Notes For Permit 01101180 |
| Permit Number |
01101180 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-05 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101180 | | | 400 NORTHPOINT PARKWAY # 401 | | | CONT: BUTTERS CONSTRUCTION | | | TEL: (954) 570-8111 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SHEET A-4 (NOTE) CARD READER- PLEASE | | | SUBMIT INFORMATION ON THE ELEC. LOCK ON | | | MAIN ENTRY DOOR THAT WILL COMPLY WITH | | | SECTION 1012.6.1 SBC., OR HOW DOOR WILL | | | UNLOCK WHEN LOSS OF POWER? HOW WOULD | | | FIRE DEPARTMENT GAIN ACCESS? SIGNAGE. | | | | | | 2)- SHEET A-4 ROOM # 116 INDICATES THAT | | | FILES & SHELVING WILL BE PART OF THIS | | | ROOM, INDICATE CLEAR FLOOR SPACE FOR | | | REQUIRED MEANS OF EGRESS. | | | | | | 3)- SBC TABLE 803.3 PROVIDE THE MINIMUM | | | INTERIOR FINISH SCHEDULE FOR BUSINESS | | | OCCUPANCY/ SPRINKLERED. | | | | | | 4)- FL ACC CODE 4.5.1 FLOOR SURFACES | | | ALONG ACCESSIBLE ROUTES AND IN ACCESS- | | | IBLE ROOMS AND SPACES INCLUDING FLOORS, | | | WALKS AND RAMPS SHALL BE FIRM AND SLIP | | | RESISTANT. COMPLY WITH ADDAAG A4.5.1 | | | A STATIC COEFFICIENT OF 0.6 IS RECOMMEND | | | ED FOR ACCESSIBLE ROUTES SND 0.8 FOR | | | RAMPS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|