2002-03-13 00:00:00THE PLANS SIGNED, SEALED AND DATED BY
 JOSEPH T. LATERZA, PE MARCH 8, 2002
 CONTINUE TO HAVE INCOMPLETE AND
 INCORRECT INFORMATION.THIS IS THE
 FIFTH REJECTION AND IS BEING FILED WITH
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
  
  
 THE LETTER ATTACHED TO THOSE PLANS
 TITLED "ATTENTION HAROLD PISKURA" SEEKS
 TO
 ADDRESS PREVIOUS REVIEW COMMENTS.THE
 ENGINEER ALLEGES "RECOGNITION" AND
 "APPROVAL" IN ACCORDANCE WITH NER
 REPORT405 AND THE METRO-DADE ACCEPTANCE
 REPORT#99-0223.07
  
 1BOTHREPORTS SPECIFY A MINIMUM OF
 20GAUGE METAL STUDS.THE LATERZA PLAN
 SPECIFIES A 25 GAUGE METAL STUD WHICH
 IS OF LESS MATERIALVALUE.
  
 2BOTH REPORTS REQUIRE THE
 INCORPORATION OF 5/8 INCH PLYWOOD
 SHEATHING SUBSTRATE AS A CONDITION OF
 USE FOR THE "HARDIPANEL" TO COMPLY WITH
 THOSE LISTINGS.HERE, THE ENGINEER
 PROPOSES THE SUBSTITUTION OF "DUROCK"
 FOR THAT OF THE PLYWOOD.LATERZA
 PROVIDES NOTHING TO DEMONSTRATE THAT
 "DUROCK" IS AN EQUAL AND ALTERNATE
 MATERIAL TO THE PLYWOOD, (STRUCTURAL
 PANELS) SPECIFIED IN THE ACCEPTANCE
 REPORTS.
  
 THE ENGINEER PROPOSES ATTACHING THE
 "DUROCK" TO THE METAL STUDS OVER TWO
 LAYERS OF TYPE X DRYWALL WITH TYPE "S"
 DRYWALL SCREWS SPACE 12" CENTER TO
 CENTER.THE "HARDIPANEL" IS THEN TO BE
 APPLIED USING "ET-F PIN 2 1/2" LONG X 0.
 10 KNURLED SHANK X 0.25 HD PIN FASTNER
 ES 4144 4" OC EDGE 8" OC FIELD ( PER
 NER-405 REPORT) SEE ATTACHED SPECS"
  
 3DUROCK, A US GYPSUM PRODUCT,HAS ITS
 OWN LISTINGS WITH RECOGNIZED AGENCIES,
 INCLUDING SBCCI.THESE WERE NOT
 INCLUDED WITH THE PLANS SUBMITTAL.
 THOSE LISTINGS FOR EXTERIOR USE OF THAT
 PRODUCT REQUIRE A PROPRIETARY OR
 CORROSION RESISTANT FASTENER AND A
 WATERPROOF BARRIER.THE FASTENER
 SPACING IN THOSE LISTINGS ARE A MAXIMUM
 OF 8" OC
 WHICH DOES NOT COMPARE FAVORABLY WITH
 THE ENGINEER'S SPECIFICATION OF AN
 DRYWALL SCREW INTENDED FOR INTERIOR USE
 AND AT A 50% GREATER SPACING.
  
 4THE ET&F PIN THAT THE ENGINEER
 PROPOSES ATTACHING THE HARDIPANEL TO
 THE WALL SYSTEM IS A PNEUMATICALLY
 DRIVEN FASTENER INTENDED FOR THE
 INSTALLATION OF GYPSUM LIKE MATERIALS
 TO METAL STUDS.
  
 TO MAKE THE ASSUMPTION THAT SUCH A
 FASTENER APPLIED IN THE "FIELD 8" OC"
 AND TO HAVE ANY STRUCTURAL VALUE WHEN
 LOADED IN WITHDRAWL, FROM DRYWALL AND
 DUROCK CANNOT BE CONSIDERED GOOD
 ENGINEERING JUDGEMENT AND IS IN DIRECT
 CONTRADICTION OF THE EVALUATION REPORTS
 THAT JOSEPH LATERZA, PE
 SAYS ARE HIS RECOGNIZED METHODOLOGIES.
  
 THE USE OF THESE PRODUCTS IS NOT
 ALLOWED UNLESS THEY ARE USED IN
 ACCORDANCE WITH THEIR LISTINGS, OR
 SUBSTANTIAL EVIDENCE AS AN ALTERNATE
 METHOD AS PROVIDED FOR IN SBC 103.7.
  
 TO DATE NEITHER OF THESE OPTIONS HAS
 BEEN ACCOMPLISHED.