2002-02-07 00:00:001) THE PLANS INDICATE THAT A ONE HOUR
 WALL IS PRESENT BETWEEN THE WAREHOUSE
 AND THE RETAIL PORTION. THE DOUBLE
 DOORS LOCATED WITHIN THIS WALL ARE NOT
 RATED. A REVIEW OF THE FIRE CODES
 INDICATES THAT A ONE HOUR FIRE WALL
 IS REQUIRED BETWEEN THE RETAIL AND
 THE WAREHOUSE THUS THE DOORS WOULD
 HAVE TO BE FIRE RATED AT LEAST 45
 MINUTES. THE BUILDING CODE REQUIRES
 AT LEAST A TWO HOUR SEPARATION BETWEEN
 STORAGE LOW HAZARD, AND OTHER
 OCCUPANCIES WHEN A MIXED OCCUPANCY
 OCCURS. PLEASE STANDARD BUILDING CODE,
 SECTION 704.1, OCCUPANCY SEPARATION
 REQUIREMENTS. PLEASE CORRECT THE PLANS
 TO THE MORE RESTRICTIVE CODE
 REQUIREMENTS.
 2) EXIT SIGNAGE AND EMERGENCY LIGHTING
 WILL BE REQUIRED.
  