| 2002-02-07 00:00:00 | 1) THE PLANS INDICATE THAT A ONE HOUR | | | WALL IS PRESENT BETWEEN THE WAREHOUSE | | | AND THE RETAIL PORTION. THE DOUBLE | | | DOORS LOCATED WITHIN THIS WALL ARE NOT | | | RATED. A REVIEW OF THE FIRE CODES | | | INDICATES THAT A ONE HOUR FIRE WALL | | | IS REQUIRED BETWEEN THE RETAIL AND | | | THE WAREHOUSE THUS THE DOORS WOULD | | | HAVE TO BE FIRE RATED AT LEAST 45 | | | MINUTES. THE BUILDING CODE REQUIRES | | | AT LEAST A TWO HOUR SEPARATION BETWEEN | | | STORAGE LOW HAZARD, AND OTHER | | | OCCUPANCIES WHEN A MIXED OCCUPANCY | | | OCCURS. PLEASE STANDARD BUILDING CODE, | | | SECTION 704.1, OCCUPANCY SEPARATION | | | REQUIREMENTS. PLEASE CORRECT THE PLANS | | | TO THE MORE RESTRICTIVE CODE | | | REQUIREMENTS. | | | 2) EXIT SIGNAGE AND EMERGENCY LIGHTING | | | WILL BE REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|