Plan Review Notes
Plan Review Notes For Permit 01101112
Permit Number 01101112
Review Stop B
Sequence Number 3
Notes
Date Text
2002-02-12 00:00:00THE CUT SHEET LABELED "JAMES HARDIE"
 DOES NOT HAVE THE INFORMATION NECESSARY
 FOR THE PRODUCT TO DETERMINE CODE
 COMPLIANCE.OBTAIN THE NER-405 REPORT
 AND DETERMINE THE PARTICULAR
 APPLICATION METHOD.
  
 PROVIDE A SPECIFIC FIRE DESIGN FOR THE
 REQUIED TWO HOUR RATED WALLS.SEE SBC
 701.5.2.THIS WAS REQUESTED IN THE
 PREVIOUS CODE COMMENTS.
  
 SHOW THE REQUIRED 2 HOUR FIRE RATED
 OCCUPANCY SEPARATION IN ACCORDANCE WITH
 SBC 704.1.1 AS PREVIOUSLY REQUESTED.
  
 PROVIDE A COPY OF THE SIGNED CONTRACT
 TOGETHER WITH A DETAILED TAKEOFF,
 INCLUDING EXTENSIONS, TO JUSTIFY THE
 DECLARED PERMIT VALUATION.
  
 PLEASE COLLATE THE PLANS INTO TWO
 CONCISE SETS.