| Plan Review Notes For Permit 01101112 |
| Permit Number |
01101112 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | THE CUT SHEET LABELED "JAMES HARDIE" | | | DOES NOT HAVE THE INFORMATION NECESSARY | | | FOR THE PRODUCT TO DETERMINE CODE | | | COMPLIANCE.OBTAIN THE NER-405 REPORT | | | AND DETERMINE THE PARTICULAR | | | APPLICATION METHOD. | | | | | | PROVIDE A SPECIFIC FIRE DESIGN FOR THE | | | REQUIED TWO HOUR RATED WALLS.SEE SBC | | | 701.5.2.THIS WAS REQUESTED IN THE | | | PREVIOUS CODE COMMENTS. | | | | | | SHOW THE REQUIRED 2 HOUR FIRE RATED | | | OCCUPANCY SEPARATION IN ACCORDANCE WITH | | | SBC 704.1.1 AS PREVIOUSLY REQUESTED. | | | | | | PROVIDE A COPY OF THE SIGNED CONTRACT | | | TOGETHER WITH A DETAILED TAKEOFF, | | | INCLUDING EXTENSIONS, TO JUSTIFY THE | | | DECLARED PERMIT VALUATION. | | | | | | PLEASE COLLATE THE PLANS INTO TWO | | | CONCISE SETS. |
|