| Plan Review Notes For Permit 01101112 |
| Permit Number |
01101112 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-03 00:00:00 | 1) THE BUILDING CODE REQUIRES A TWO | | | HOUR SEPARATION BETWEEN THE WAREHOUSE | | | AND THE RETAIL AREA. THE FIRE CODE | | | REQUIRES A ONE HOUR FIRE RATING BETWEEN | | | THE WAREHOUSE AND THE RETAIL AREA. SINCE | | | THE BUILDING CODE IS MORE RESTRICTIVE | | | THEN IT SHALL APPLY IN THIS SITUATION. | | | 2) ARE THE DOORS THAT SWING INWARD | | | FIRE RATED. | | | 3) IS THE WAREHOUSE THE SAME TENANT | | | AS THE RETAIL AREA OR ARE THEY | | | DIFFERENT. PLEASE ADVISED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|