Plan Review Notes
Plan Review Notes For Permit 01101112
Permit Number 01101112
Review Stop B
Sequence Number 2
Notes
Date Text
2002-01-07 00:00:00THE EXTERIOR WALL ON THE NORTH ELEVATION
 IS REQUIRED TO BE 2 HR FIRE RATED WITH
 OPENING PROTECTIVES.SEE SBC TABLE 600
 FOR TYPE V CONSTRUCTION, EXTERIOR
 NON-BEARING WALLS, OVER 3FT TO 10FT.
 SEE ALSOFOOTNOTES (B) AND (C).REVISE
 AS NECESSARY, INCLUDE THE FIRE DESIGN
 NUMBER, SEE SBC 701.5.2.THIS WAS NOTED
 ON THE 11/13/01 COMMENT LIST.
  
  
  
 PLEASE PROVIDE INFORMATION ON THE "HARDI
 BOARD" SIDING AS TO ITS SUITABILITY AS
 A STRUCTURAL SHEATHING.
  
 WHAT IS THE NATURE AND CHARACTER OF THE
 GOODS TO BE STORED IN THE WAREHOUSE?
 SEE SBC 104.2 AND SBC 312.2.
  
 SHOW THE FIRE DESIGN FOR THE MIXED
 OCCUPANCY SEPARATION.SEE SBC 704.1.1,
 INCLUDE THE OPENING PROTECTIVES.
  
 SHEET 3 OF 4 WIND LOAD SCHEDULE, SHOWS
 PRESSURES RANGING FROM 0.5 TO 2.087.
 SBC1606.2.2.3. PROHIBITS DESIGN USING
 LESS THAN 10 PSF FOR ANY PART OF A
 BUILDING.PROVIDE COMPLETE, SIGNED,
 SEALED AND DATED CALCULATIONS FOR THE
 WIND LOAD ANALYSIS.
  
 PROVIDE A COPY OF THE SIGNED CONTRACT
 TOGETHER WITH A DETAILED TAKEOFF TO
 JUSTIFY THE $22,000.00 VALUATION.THIS
 WAS PREVIOUSLY REQUESTED.
  
 THE "NEW" PLAN SETS DO NOT HAVE SHEET 4
 OF 4.