Plan Review Notes
Plan Review Notes For Permit 01101112
Permit Number 01101112
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-03 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE 1 TOILET ROOMS ARE NOT LARGE
 ENOUGH. ROOM TO COMPLY WITH FACBC SEC
 4.22. SHOW COMPLIANCE WITH ALL CLEAR
 FLOOR SPACE, TURNING RADIUS ECT.
 4.16 W/C - FIGURE 28 (MINIMUM 7'5")
 4.19 LAV - FIGURE 31.
 2) PAGE 1 DRINKING FOUNTAINS ARE REQUIR-
 ED FOR EACH TENANT SPACE PER SPC TABLE
 407. SHOW DETAILS FOR COMPLIANCE FACBC
 SEC 4.15 AND SEC 4.1.3(10) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IN HI/LOW NOT INSTALLED.
 3) SEPARATE METERS AND RPZ BACKFLOW PRE-
 VENTER REQUIRED FOR WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377