| Plan Review Notes For Permit 01101112 |
| Permit Number |
01101112 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-25 00:00:00 | 1) PLEASE PROVIDE A SITE PLAN FOR | | | REVIEW. | | | 2) TENANT SPACE 2 APPEARS TO EXIT INTO | | | WAREHOUSE SPACE # 3. PLEASE EXPLAIN. | | | 3) EXISTING CONCRETE STAIRS ARE FOR | | | WHAT. PLEASE CLARIFY. | | | 4) WALL SHOWN BETWEEN TENANTS 1 & 2 AND | | | WAREHOUSE SPACE 3 RATED? | | | 5) ROLL-UP DOOR BEING SHOWN AS AN EXIT. | | | THIS ARRANGEMENT IS NOT PERMITTED. | | | 6) INTERIOR FINISH FOR WALLS AND | | | CEILINGS REQUIRED. | | | 7) PLEASE EXPLAIN EXITING FROM | | | WAREHOUSE SPACE # 3. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|