| 2001-11-05 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2)NOTE: PLEASE SHOW LOAD CALCUALTIONS |
| | AND SHOW ALL CONTINUOS LOADS AT 125% |
| | 215-5/230-42/215-3 ECT. |
| | |
| | 3)NOTE: PLANS NEED TO HAVE ALL BRANCH |
| | CIRCUIT #`S SHOWN ON PLANS AND CORRELATE |
| | WITH SUBMITTED PANEL SCHEDULES. |
| | |
| | 4)NOTE: PLEASE NOTE THAT PLANS ARE |
| | SHOWING THREE NEW SERVICES? PLEASE NOTE |
| | ONLY ONE HOUR SEPARATION BETWEEN 1&2, |
| | SEPARATE SERVICES MAY BE USED BUT MUST |
| | MEET TWO HOUR RATING. PLEASE CLARIFY |
| | RATING BETWEEN 2&3? |
| | PLEASE CALRIFY EXITING FROM SPACE 2 TO |
| | SPACE 3?? |
| | |
| | 5)NOTE: PLEASE NOTE OUTLETS ABOVE WINDOW |
| | S ARE NOTED FOR SIGNS? PLEASE NOTE THESE |
| | OUTLETS NEED TO MEET 210-62 FOR SHOW |
| | WINDOW(S). AND CIRCUIT REQ`D FOR SIGN(S) |
| | ARE TO MEET 600-5. |
| | PLEASE ADJUST. |
| | |
| | 6) PLEASE CLARIFY EQUIPMENT GROUNDING |
| | METHOD BETWEEN FIRST MEANS OF DISCONNECT |
| | AND PANEL(S). EQUIPMENT GROUNDING |
| | CONDUCTORS ARE TO BE SIZED BY 250-122. |
| | |
| | 7)NOTE: PLEASE NOTE MISSING CONDUCTORS |
| | FOR SERVICE METER TO MAIN AND MAIN TO |
| | PANEL.? CONDUIT SIZES? 215-5 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |