2001-11-05 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 AND SHOW ALL CONTINUOS LOADS AT 125%
 215-5/230-42/215-3 ECT.
  
 3)NOTE: PLANS NEED TO HAVE ALL BRANCH
 CIRCUIT #`S SHOWN ON PLANS AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULES.
  
 4)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING THREE NEW SERVICES? PLEASE NOTE
 ONLY ONE HOUR SEPARATION BETWEEN 1&2,
 SEPARATE SERVICES MAY BE USED BUT MUST
 MEET TWO HOUR RATING. PLEASE CLARIFY
 RATING BETWEEN 2&3?
 PLEASE CALRIFY EXITING FROM SPACE 2 TO
 SPACE 3??
  
 5)NOTE: PLEASE NOTE OUTLETS ABOVE WINDOW
 S ARE NOTED FOR SIGNS? PLEASE NOTE THESE
 OUTLETS NEED TO MEET 210-62 FOR SHOW
 WINDOW(S). AND CIRCUIT REQ`D FOR SIGN(S)
 ARE TO MEET 600-5.
 PLEASE ADJUST.
  
 6) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 7)NOTE: PLEASE NOTE MISSING CONDUCTORS
 FOR SERVICE METER TO MAIN AND MAIN TO
 PANEL.? CONDUIT SIZES? 215-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW