Plan Review Notes
Plan Review Notes For Permit 01101112
Permit Number 01101112
Review Stop B
Sequence Number 1
Notes
Date Text
2001-11-13 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
 SIGNED SEALED AND DATED.
  
 THE CONVERSION AND ENCLOSING OF THE
 LOADING DOCK IS SUBJECT TO IMPACT FEES
 COLLECTED BY THE COUNTY FOR THE CITY.
 THE PERMIT PLANS MUST BE STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025FOR
 MORE INFORMATION.
  
 THIS BUILDING IS LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND TYPE VI
 (COMBUSTIBLE PLYWOOD SHEATHING) IS
 PROHIBITTED.
  
 IT APPEARS FROM THE SITE PLAN, SUBJECT
 TO VERIFICATION BY SURVEY, THAT THE NEW
 EXTERIOR WALLS ON THE NORTH AND EAST
 ELEVATIONS ARE REQUIRED BY SBC TABLE
 600 TO BE AT LEAST 2 HR FIRE RATED WITH
 OPENING PROTECTIVES FOR THIS BUILDINGS'
 TYPE V CONSTRUCTION.PLEASE REVISE AS
 NECESSARY.
  
 SEE ALSO SBC 704.5.2 PARAPET WALL
 REQUIRMENTS.
  
 WHAT IS THE NATURE AND QUANTITY OF GOODS
 TO BE STORED IN THE WAREHOUSE? SEE SBC
 104.2 AND SBC 312.2.
  
 WHAT IS THE INTENDED USE OF TENANT
 SPACES 1 AND 2? SEE SBC 104.2.
  
  
 SBC 704.1.1 REQUIRES A MIXED OCCUPANCY
 SEPARATION BETWEEN THE WAREHOUSE AND
 THE OTHER SPACES. (2 HR MIN)
  
 WHAT IS THE GAUGE AND TYPE OF 6" METAL
 STUDS AND TOP AND BOTTOM CHANNELS TO BE
 USED?
  
 SPECIFY THE SIZE AND TYPE OF WELDS TO BE
 USED TO CONNNECT THE TOP CHANNEL TO THE
 EXISTING BEAM.
  
 PROVIDE A WINDOW AND DOOR BUCK ANCHORING
 DETAIL.
  
 SHOW THE DESIGN PRESSURES FOR THE
 STOREFRONT, ROLL UP DOOR AND ROOF
 COVERING.SHOW HOW THE GLAZED AREAS
 WILL COMPLY WITH THE CITY'S HURRICANE
 MISSILE IMPACT ORDINANCE.ALSO, IF
 COMPLETE PRODUCT INFORMATION IS NOT
 PROVIDED WITH THIS PERMIT APPLICATION,
 SEPARATE PERMITS AND FEES WILL BE
 REQUIRED FOR THAT WORK.
  
 PROVIDE CONFIRMATION THAT THE EXISTING
 STAIRS MEET THE REQUIREMENTS OF SBC
 1007 OR DETAILS TO MODIFY AS NECESSARY
 FOR ALL OF THOSE REQUIREMENTS.
  
 SHOW A DETAIL FOR THE CONSTRUCTION OF
 THE DUMPSTER WALL.
  
 THE PAIR OF DOORS FROM TENANT SPACE #2
 OBSTRUCT EGRESS FROM THE WAREHOUSE,
 SEE SBC 1012.1.5.
  
 THE DECLARED VELOCITY PRESSURE OF 25PSF
 DOES NOT AGREE WITH THE STATED ROJOF
 HEIGHT OF 35'.PLEASE CLARIFY.
  
 THE $22,000.00 VALUATION IS TOO LOW FOR
 THIS SCOPE OF WORK.PROVIDE A COPY OF
 THE SIGNED CONTRACT TOGETHER WITH A
 DETAILED TAKEOFF INCLUDING EXTENSIONS.