| Date |
Text |
| 2001-11-13 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY |
| | SIGNED SEALED AND DATED. |
| | |
| | THE CONVERSION AND ENCLOSING OF THE |
| | LOADING DOCK IS SUBJECT TO IMPACT FEES |
| | COLLECTED BY THE COUNTY FOR THE CITY. |
| | THE PERMIT PLANS MUST BE STAMPED BY |
| | THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025FOR |
| | MORE INFORMATION. |
| | |
| | THIS BUILDING IS LOCATED IN THE |
| | DESIGNATED FIRE DISTRICT AND TYPE VI |
| | (COMBUSTIBLE PLYWOOD SHEATHING) IS |
| | PROHIBITTED. |
| | |
| | IT APPEARS FROM THE SITE PLAN, SUBJECT |
| | TO VERIFICATION BY SURVEY, THAT THE NEW |
| | EXTERIOR WALLS ON THE NORTH AND EAST |
| | ELEVATIONS ARE REQUIRED BY SBC TABLE |
| | 600 TO BE AT LEAST 2 HR FIRE RATED WITH |
| | OPENING PROTECTIVES FOR THIS BUILDINGS' |
| | TYPE V CONSTRUCTION.PLEASE REVISE AS |
| | NECESSARY. |
| | |
| | SEE ALSO SBC 704.5.2 PARAPET WALL |
| | REQUIRMENTS. |
| | |
| | WHAT IS THE NATURE AND QUANTITY OF GOODS |
| | TO BE STORED IN THE WAREHOUSE? SEE SBC |
| | 104.2 AND SBC 312.2. |
| | |
| | WHAT IS THE INTENDED USE OF TENANT |
| | SPACES 1 AND 2? SEE SBC 104.2. |
| | |
| | |
| | SBC 704.1.1 REQUIRES A MIXED OCCUPANCY |
| | SEPARATION BETWEEN THE WAREHOUSE AND |
| | THE OTHER SPACES. (2 HR MIN) |
| | |
| | WHAT IS THE GAUGE AND TYPE OF 6" METAL |
| | STUDS AND TOP AND BOTTOM CHANNELS TO BE |
| | USED? |
| | |
| | SPECIFY THE SIZE AND TYPE OF WELDS TO BE |
| | USED TO CONNNECT THE TOP CHANNEL TO THE |
| | EXISTING BEAM. |
| | |
| | PROVIDE A WINDOW AND DOOR BUCK ANCHORING |
| | DETAIL. |
| | |
| | SHOW THE DESIGN PRESSURES FOR THE |
| | STOREFRONT, ROLL UP DOOR AND ROOF |
| | COVERING.SHOW HOW THE GLAZED AREAS |
| | WILL COMPLY WITH THE CITY'S HURRICANE |
| | MISSILE IMPACT ORDINANCE.ALSO, IF |
| | COMPLETE PRODUCT INFORMATION IS NOT |
| | PROVIDED WITH THIS PERMIT APPLICATION, |
| | SEPARATE PERMITS AND FEES WILL BE |
| | REQUIRED FOR THAT WORK. |
| | |
| | PROVIDE CONFIRMATION THAT THE EXISTING |
| | STAIRS MEET THE REQUIREMENTS OF SBC |
| | 1007 OR DETAILS TO MODIFY AS NECESSARY |
| | FOR ALL OF THOSE REQUIREMENTS. |
| | |
| | SHOW A DETAIL FOR THE CONSTRUCTION OF |
| | THE DUMPSTER WALL. |
| | |
| | THE PAIR OF DOORS FROM TENANT SPACE #2 |
| | OBSTRUCT EGRESS FROM THE WAREHOUSE, |
| | SEE SBC 1012.1.5. |
| | |
| | THE DECLARED VELOCITY PRESSURE OF 25PSF |
| | DOES NOT AGREE WITH THE STATED ROJOF |
| | HEIGHT OF 35'.PLEASE CLARIFY. |
| | |
| | THE $22,000.00 VALUATION IS TOO LOW FOR |
| | THIS SCOPE OF WORK.PROVIDE A COPY OF |
| | THE SIGNED CONTRACT TOGETHER WITH A |
| | DETAILED TAKEOFF INCLUDING EXTENSIONS. |