2001-10-26 00:00:00CHECKLIST:
  
 1-CONSTRUCTION VALUE DECLARED WAS TOO
 LOW. IT WAS ADJUSTED TO $3000. TO
 REFLECT LABOR AND MATERIALS.
 -OWES $11.22 FOR UPDATED VALUE & RADON
 FEES. PLEASE BRING PAID RECEIPT.
 2-NEED TO RECORD NOTICE OF COMMENCEMENT
 IN THE COURTHOUSE.
 3-ENGINEER TO REVISE THE DESIGN
 CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM. THE MEAN ROOF HEIGHT
 AND VELOCITY PRESSURE DON'T MATCH:
 SEE TABLE 1606.2A ON THE SBC 1997.
 ALSO, REVISE THE IMPORTANCE FACTOR:
 SEE TABLE 1606 OF SBC 1997.
 4-ENGINEER TO PROVIDE COMPLETE SPECS FOR
 STRUCTURAL GUTTER.
 5-DIMENSIONS GIVEN ON THE ENGINEER'S
 DRAWINGS AND THE SURVEY DON'T MATCH.
 SEE SURVEY AND REVISE ACCORDINGLY.
 6-IF SCREEN AREA WILL HAVE A DOOR, THEN
 SPECIFY SIZE IN ORDER TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS
 OF TABLE 1004 OF SBC 1997.