| Plan Review Notes For Permit 01101097 |
| Permit Number |
01101097 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-29 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT G-A2.0 SANITARY ISOMETERIC DETAIL | | | TWO WAY C/O REQD NEAR JUNCTION OF BLDG | | | DRAIN AND BLDG SEWER. | | | 2) SHT G-A2.0 WATER ISOMETERIC AIR | | | CHAMBERS REQUIRE ACCESS AND MUST BE RE- | | | CHARGED. APPROVED WATER HAMMER ARRESTORS | | | DO NOT REQUIRE ACCESS PANELS. PLEASE | | | SHOW DETAILS. | | | 3) SHT G-A2.0 3" VTR REQUIRED CAN NOT | | | RUN THROUGH TIE BEAM PER SBC-97 SEC | | | 1907.3.5. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|