| Plan Review Notes For Permit 01101097 |
| Permit Number |
01101097 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-24 00:00:00 | 1) WILL THE GUARD-HOUSE ALWAYS BE | | | STAFFED 24 HOURS A DAY, SEVEN DAYS | | | A WEEK, 365 DAYS A YEAR. | | | 2) WHAT PROVISIONS HAVE BEEN MADE FOR | | | FIRE RESCUE ACCESS. | | | 3) THERE ARE SEVERAL MEDIANS SHOWN. FIRE | | | CODES REQUIRES AT LEAST 20 FEET IN | | | CLEAR WIDTH. PLEASE DEMONSTRATE | | | COMPLIANCE. | | | 4) WHAT PROVISIONS HAVE BEEN MADE FOR | | | LOSS OF POWER. | | | 5) A MINIMUM OF 13'- 6" IS REQUIRED IF | | | FIRE APPARATUS ARE EXPECTED TO PASS | | | UNDER THE OVERHANGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|