| Plan Review Notes For Permit 01101096 |
| Permit Number |
01101096 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-31 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101096 | | | 2000 PALM BEACH LAKES # 302 | | | CONT: LEIGHTON & MC GINN | | | TEL: 662-6609 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)- FL ACC CODE 4.13.6 MANEUVERING CLEAR | | | ENCES AT DOORS REQUIRES 18" ON THE PULL | | | SIDE OF DOORS, 12" PUSH. | | | | | | 2)- SBC 704.2.1.4 EXIT ACCESS CORRIDORS, | | | FIRE RATED WALLS RREQUIRED TO HAVE PRO- | | | TECTED OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANENTLY IDENTIFIED WWITH SIGNAGE OR | | | STENCILING, SUGESTED WORDS" FIRE/ SMOKE | | | BARRIER PROTECT ALL OPENINGS". | | | | | | 3)- SBC TABLE 803.3 MINIMUM INTERIOR | | | FINISH CLASSIFICATION SCHEDULE | | | | | | 4)- SBC 1016.2-1016.3 MISSING EMERGENCY | | | LIGHTING & EXIT INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|