| 2001-10-16 00:00:00 | DENIED | | | 1. DUCT SHALL NOT BE LOCATED IN | | | STAIRWELL | | | 2. NO RETURN SHOWN FOR FIRST FLOOR FROM | | | RTU 1 | | | 3. FAN SHUT DOWN BY DUCT SMOKE | | | DETECTORSREQUIRED. | | | 4. LOCATION AND INSTALLATION DETAILS FOR | | | FIRE DAMPERS SHALL BE PROVIDED ON PLANS | | | BY THE DESIGNER. | | | 5. PROVIDE CALCULATIONS SHOWING | | | COMPLIANCE WITH ASHRAE 62-89 OUTSIDE | | | AIR REQUIREMENTS. | | | 6. PROVIDE DETAILS FOR RTU'S ON ROOF | | | SHOWING ATTACHMENT AND PENETRATION | | | REQUIREMENTS. | | | 7. SPECIFY DUCT MATERIAL AND R-VALUE | | | 8. PROVIDE ENERGY EFFICIENCY VALUES FOR | | | EQUIPMENT. |
|