Plan Review Notes
Plan Review Notes For Permit 01101066
Permit Number 01101066
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-16 00:00:00DENIED
 1. DUCT SHALL NOT BE LOCATED IN
 STAIRWELL
 2. NO RETURN SHOWN FOR FIRST FLOOR FROM
 RTU 1
 3. FAN SHUT DOWN BY DUCT SMOKE
 DETECTORSREQUIRED.
 4. LOCATION AND INSTALLATION DETAILS FOR
 FIRE DAMPERS SHALL BE PROVIDED ON PLANS
 BY THE DESIGNER.
 5. PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH ASHRAE 62-89 OUTSIDE
 AIR REQUIREMENTS.
 6. PROVIDE DETAILS FOR RTU'S ON ROOF
 SHOWING ATTACHMENT AND PENETRATION
 REQUIREMENTS.
 7. SPECIFY DUCT MATERIAL AND R-VALUE
 8. PROVIDE ENERGY EFFICIENCY VALUES FOR
 EQUIPMENT.