| Plan Review Notes For Permit 01101061 |
| Permit Number |
01101061 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-30 00:00:00 | DENIED | | | REFERENCES: SPC-94 - FACBC-97 | | | | | | 1) SUBMIT CALCULATIONS FOR MINIMUM FAC- | | | ILITIES PER SPC TABLE 407. PAGE 3.1 | | | 2) PAGE MP-1 DRINKING FOUNTAIN. PLEASE | | | SHOW DRINKING FOUNTAIN DETAIL TO SHOW | | | COMPLIANCE WITH FACBC-97 SEC 4.15. IF A | | | SINGLE DRINKING FOUNTAIN SPOUT TO BE 36" | | | OFF FLOOR AND PROVISIONS SHALL BE MADE | | | FOR THOSE THAT HAVE DIFFICULTY BENDING | | | OR STOOPING. | | | 3) PAGE MP-1 WATER RISER. WATER HAMMER | | | ARRESTORS SHALL BE INSTALLED PER MANU- | | | FACTURE INSTALLATION INSTRUCTIONS AND | | | WH-PDI 201. ARRESTORS SHALL BE LOCATED | | | NEAR FIXTURES NOT AT TOP OF DROP AS IN- | | | DICATED ON RISER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|