Plan Review Notes
Plan Review Notes For Permit 01101061
Permit Number 01101061
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-30 00:00:00DENIED
 REFERENCES: SPC-94 - FACBC-97
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER SPC TABLE 407. PAGE 3.1
 2) PAGE MP-1 DRINKING FOUNTAIN. PLEASE
 SHOW DRINKING FOUNTAIN DETAIL TO SHOW
 COMPLIANCE WITH FACBC-97 SEC 4.15. IF A
 SINGLE DRINKING FOUNTAIN SPOUT TO BE 36"
 OFF FLOOR AND PROVISIONS SHALL BE MADE
 FOR THOSE THAT HAVE DIFFICULTY BENDING
 OR STOOPING.
 3) PAGE MP-1 WATER RISER. WATER HAMMER
 ARRESTORS SHALL BE INSTALLED PER MANU-
 FACTURE INSTALLATION INSTRUCTIONS AND
 WH-PDI 201. ARRESTORS SHALL BE LOCATED
 NEAR FIXTURES NOT AT TOP OF DROP AS IN-
 DICATED ON RISER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377