2001-10-29 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE DETAIL SHOWING HOW
 CONDENSER UNIT STAND WILL BE ATTACHED
 TO THE ROOF.PLEASE NOTE 18" MINIMUM
 BETWEEN THE ROOF SURFACE TO THE BOTTOM
 OF THE SUPPORT RAIL.
  
 PLEASE INDICATE TERMINATION OF EMERGENCY
 DRAIN FROM THE AUXILIARY DRAIN PAN.
 TERMINATION SHALL BE AT A CONSPICUOUS
 POINT TO SERVE AS AN ALARM THAT THE
 REGULAR DRAIN IS RESTRICTED. 1997 SMC
 304.8.6.1.
  