2001-11-27 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE A COMPLETED DESIGN COMPLIANCE
 FORM OR PROVIDE ALL OF THE DESIGN
 PARAMETERS AND ASSUMPTIONS ON THE PLANS.
 SUCH AS BUILDING HEIGHT,MEAN ROOF HEIGHT
 BASIC VELOCITY PRESSURE, ETC. SEE FORM
 ATTACHED.
  
 4) PROVIDE EGRESS DOORS IN THE EXIT
 ACCESS WITH A CLEAR OPENING OF NOT LESS
 THAN 32" WIDE AND SHALL BE OF THE SIDE
 SWINGING TYPE. 97 SBC 1012.1.1, 1012.1.2
  
 5) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED IN EXTERIOR WALL WITHIN 0-3 FT.
 OF PROPERTY LINE PER 97 SBC TABLE 600 &
 SEC. 2112.1.2
  
 6) GLASS BLOCK IN MASTER BATHROOM AND
 BATH #2 IS LOCATED IN A HAZARDOUS
 LOCATION AND IS REQUIRED TO HAVE A
 MINIMUM UNIFORM FACE THICKNESS OF
 0.25 INCH PER SBC 2405.2.
  
 7) DETAIL NUMBER 38 ON A-13 SHOWS THE
 BOTTOM OF THE FOOTING AT 8" BELOW GRADE,
 THE CODE REQUIRES THE BOTTOM OF THE
 FOOTING TO BE A MINIMUM OF 12" BELOW
 GRADE. SBC 1804.1.3.
  
 8) THE BENDING DIAGRAM ON A-13 IS
 PRINTED UPSIDE DOWN AND BACKWARDS.
  
 9) PROVIDE UL LISTING INFORMATION AND
 MANUFACTURERS SPECIFICATIONS FOR BBQ.
 97SBC 2808
  
 10) PROVIDE ACCESS TO ATTIC SPACE FROM
 SECOND FLOOR PER 97 SBC SEC. 2309.6.
  
 11) PROVIDE DETAILS FOR STAIRS,HANDRAILS
 AND GUARDRAILS. INDICATE RISER & TREAD
 DIMENSIONS, HANDRAIL DIMENSIONS & HEIGHT
 AND GUARDRAIL HEIGHT, INTERMEDIATE RAIL
 SPACING, ATTACHMENTS, ETC. 97 SBC SEC.
 1007.3, 1007.5, 1015 AND 1608.2
  
 12) INDICATE FIREBLOCKING AT STAIRS PER
 97 SBC 2305.1.4.
  
 13) INDICATE THE LENGTH OF THE 1/2"
 ANCHOR BOLTS USED TO ATTACH THE 2X6 P.T.
 ON THE GARAGE DOOR JAMB DETAIL ON A-6.
  
 14) CLARIFY HOW THE (2) 8X22 L-6 LINTELS
 WILL BEAR ON THE C-9 STEEL COLUMN AND
 COMPLY WITH THE 4" MINIMUM END BEARING
 REQUIRED BY CODE. 97 SBC 2101.3.1
  
 15) THE DIMENSIONS FOR DETAIL 19 ON A-14
 ARE MISPRINTED.
  
 16) DETAIL 21 ON A-14 IS MISSING THE
 DIMENSIONS FOR HEIGHT AND BOLT SPACING.
  
 17) THE TRUSS CONNECTOR SCHEDULE ON A-14
 LISTS SEMCO CONNECTORS, PLEASE NOTE THAT
 SEMCO HAS BEEN PURCHASED BY USP AND THE
 CAPACITIES MAY HAVE CHANGED.
  
 18) GLASS BLOCK COMPLYING WITH 97 SBC
 SEC. 2112 ARE NOT REQUIRED TO BE
 SHUTTERED. REVIEW #16 ON KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
  
 19) INDICATE ON PLANS THAT ADEQUATE
 SUBSTRATE FOR ANCHORING STORM PANELS
 WILL BE PROVIDED AT GLAZED OPENINGS IN
 WOOD FRAME SECTION OF STRUCTURE.
  
 20) INDICATE THE SPECIFIC ANCHORS THAT
 WILL BE TO ANCHOR THE STORM PANELS TO
 THE WOOD FRAME PORTION OF THE STRUCTURE.
  
 21) PROVIDE CURRENT PRODUCT APPROVAL FOR
 ROOF TILE AND SINGLE HUNG WINDOWS. THE
 ONES SUBMITTED HAD EXPIRED PRIOR TO
 APPLYING FOR PERMIT.
  
 22) PROVIDE PRODUCT APPROVALS FOR ARCHED
 TOP FIXED GLASS WINDOWS.
  
 23) PROVIDE PRODUCT APPROVALS FOR ALL
 COMPONENTS USED IN THE LARGE FIXED GLASS
 WINDOW ASSEMBLY AT THE LIVING ROOM. THE
 COMPONENTS MUST BE TESTED AND APPROVED
 FOR THIS TYPE OF ASSEMBLY AND MEET OR
 EXCEED THE REQUIRED WIND LOADS. PLEASE
 PROVIDE ADDITIONAL DETAILS THAT INDICATE
 THE VARIOUS COMPONENTS AND HOW THEY ARE
 ATTACHED TO EACH OTHER & THE STRUCTURE.
  
 24) THE MASONRY OPENING DIMENSIONS GIVEN
 ON A-4 FOR THE LARGE FIXED GLASS WINDOW
 DO NOT APPEAR TO BE CORRECT. PLEASE
 REVIEW M.O. DIMENSIONS AND POSITIVE AND
 NEGATIVE PRESSURES FOR THIS WINDOW.
  
 25) PROVIDE A COMPLETED CITY OF W.P.B.
 SITE SPECIFIC PRODUCT APPROVAL FORM FOR
 THE TWO FIXED GLASS WINDOWS AT STEEL
 COLUMN AT BREAKFAST ROOM, IN ADDITION TO
 THE DRAWING SUBMITTED BY THE ENGINEER.
 THE COMPLETED FORM MUST BE SIGNED,SEALED
 AND DATED BY THE ENGINEER CERTIFYING THE
 COMPONENTS AND BY THE DESIGNER OF RECORD
 OF THE STRUCTURE ACKNOWLEDGING THAT THE
 PRODUCT AND INSTALLATION WILL BE
 SUFFICIENT TO COMPLY WITH CODE REQUIRE-
 MENTS FOR INSTALLATION IN HIS STRUCTURE.
 (FORM ATTACHED)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202