2001-11-24 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE LEFT ELEVATION DOES NOT COMPLY
 WITH TABLE 600 (97 SBC) FOR THE SECTION
 OF EXTERIOR WALL THAT IS 3'-2" OFF THE
 PROPERTY LINE. PER THE TABLE, 20% OF THE
 FLOOR TO CEILING WALL AREA IS ALLOWED AS
 OPENINGS.
  
 4) SAFETY GLASS IS REQUIRED IN THE
 LAUNDRY ROOM WINDOW BECAUSE IT IS
 LOCATED WITHIN A 24" RADIUS OF THE DOOR
 IN A CLOSED POSITION. 97SBC 2405.2
  
 5) THE 97 FLORIDA ACCESSIBILTY CODE FOR
 BUILDING CONSTRUCTION REQUIRES TOILET
 FACILITIES TO BE ACCESSIBLE. THE DOOR TO
 THE TOILET LOCATED IN THE MASTER BATH
 MUST ALSO HAVE A 29" CLEAR OPENING IN
 ORDER TO COMPLY WITH ACCESSIBILITY
 REQUIREMENTS. 4.22 OF FL ACCESSIBILITY
 CODE
  
 6) THE 1/2 SH 35 WINDOWS IN BEDROOM #3
 DO NOT MEET THE EGRESS REQUIREMENTS.
 SECOND STORY EGRESS WINDOWS MUST HAVE A
 MINIMUM NET CLEAR OPENING AREA OF 5.7
 SQUARE FT. 97 SBC 1005.4.4.
  
 7) THE WINDOW IN BATH #3 IS REQUIRED TO
 BE SAFETY GLASS IF LOCATED LESS THAN 60"
 ABOVE THE DRAIN INLET FOR THE TUB.
 97SBC 2405.2
  
 8) STAIRS MUST COMPLY WITH 1007.3.1 OF
 97SBC; THE SUM OF TWO RISERS AND A TREAD
 EXCLUSIVE OF THE PROJECTION OF THE
 NOSING SHALL BE NOT LESS THAN 24" NOR
 MORE THAN 25". PLEASE CORRECT.
  
 9) STAIRS MUST BE FIREBLOCKED. 97SBC
 705.3, 2305.1 AND 1007.1.3
  
 10) STAIR WINDERS SHALL HAVE A MINIMUM
 TREAD DEPTH OF 6" AT THE NARROW EDGE AND
 SHALL HAVE A MINIMUM TREAD DEPTH OF 11"
 AT A POINT 12" FROM THE NARROW EDGE.
 97 SBC 1007.8
  
 11) PROVIDE STRUCTURAL DETAILS FOR WALL
 THAT IS SHOWN BETWEEN GOLF CART GARAGE
 AND CAR GARAGE. INCLUDE FOOTING, STEEL
 REINFORCING, ETC.
  
 12) PROVDE STRUCTURAL DETAILS FOR THE
 KNEE WALLS AND DECORATIVE GUARDRAIL AT
 THE BALCONY OUTSIDE BEDROOM #3. INCLUDE
 ATTACHMENT DETAILS, INTERMEDIATE RAIL
 SPACING, ETC.
  
 13) PROVIDE STRUCTURAL DETAILS OF THE
 TUBE STEEL HEADERS INDICATED ON SHT.A-7
 AND INSTALLED BETWEEN SGD AND FIXED
 GLASS WINDOWS.
  
 14) PROVIDE BASE PLAT DIMENSIONS AND
 ANCHOR INFORMATION FOR COLUMN C-9.
  
 15) THE NOTE ON A-9 REFERS TO THE
 DIAPHRAGM SCHEDULE ON SHT. A-5. IT IS
 LOCATED ON SHT. A-10. PLEASE CORRECT.
  
 16) INDICATE THE CONNECTORS FOR THE
 UPLIFTS (1943#,1394#,358#) AT THE GARAGE
 ON SHT. A-9.
  
 17) THE CONNECTOR FOR THE GIRDER TRUSS
 AT THE COVERED PATIO WITH 2148# UPLIFT
 REFERS TO DETAIL 32 ON A-14. THERE IS NO
 DETAIL 32 ON A-14. PLEASE CORRECT.
  
 18) SPECIFY THE UPLIFT AND CONNECTORS
 FOR THE HIP TRUSSES ON SHT. A-10.
  
 19) THE NOTE ON A-10 REFERS TO THE
 DIAPHRAM SCHEDULE ON A-5, HOWEVER, IT IS
 LOCATED ON A-10. PLEASE CORRECT.
  
 20) THE TRUSS WITH 857# UPLIFT AT THE
 SECOND FLOOR MASTER BEDROOM REFERS TO
 DETAIL 4 ON A-14, WHICH IS A WOOD WALL
 TO MASONRY WALL CONNECTION DETAIL.
 PLEASE CORRECT.
  
 21) SPECIFY CONNECTOR FOR TRUSS WITH
 1747# UPLIFT AT SECOND FLOOR ABOVE
 LIVING ROOM / DINING ROOM AREA.
  
 22) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRENCH DOORS
 - ROOFING MATERIAL FOR CONCRETE BALCONY
 - ROOF TILE EXPIRED 10-01-01(PRIOR TO
 SUBMITTING FOR PERMIT)
 - 4000 SERIES SH WINDOWS EXPIRED 10-5-01
 (PRIOR TO SUBMITTING FOR PERMIT)
  
 23) INDICATE GLASS BLOCK WITH A MINIMUM
 UNIFORM FACE THICKNESS OF 0.25 INCH FOR
 INSTALLATION AT SHOWER IN MASTER BATH
 ROOM. 97SBC 2405.2.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202