| Plan Review Notes For Permit 01100954 |
| Permit Number |
01100954 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-01-10 00:00:00 | SUBMITTAL CHECKLIST: | | | 1-TRUSS DRAWINGS ARE OK, BUT ARCHITECT | | | NEEDS TO SPECIFY CONNECTOR FOR TRUSS | | | H-7 THAT WILL RESIST THE UPLIFT LOADS | | | CALCULATED ON ENGINEERED TRUSS. | | | -ALSO, ARCHITECT TO SPECIFY HURRICANE | | | ANCHORS FOR ROOF TRUSSES RESTING AT | | | NEW 2X10 BEAMS. | | | 2-ARCHITECT TO SPECIFY CAP CONNECTOR AT | | | NEW 4"X4" CORNER WOOD COLUMN. | | | 3-PROVIDE PRODUCT APPROVAL (2 COPIES)FOR | | | A)NON-IMPACT OVAL WINDOW. | | | B)NON-IMPACT SINGLE HUNG WINDOWS. | | | (MISSING PAGE 2 OF 3 AND DRAWINGS ARE | | | NOT LEGIBLE). | | | C)NON-IMPACT FRENCH DOORS. | | | (MISSING ONE DRAWING AND DRAWINGS ARE | | | NOT LEGIBLE). | | | D)STORM SHUTTERS: | | | -DRAWINGS ARE NOT LEGIBLE. | | | -INDICATE ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE AND SPACING | | | TO BE USED IN THIS PROJECT. |
|