| 2001-11-09 00:00:00 | APPROVED WITH PROVISO: |
| | 1-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM: |
| | -MEAN ROOF HEIGHT AND BASIC VELOCITY |
| | PRESSURE DON'T MATCH. SEETABLE |
| | 1606.2A SBC 1997. |
| | 2-MASTER BEDROOM 34 SH WINDOW DOESN'T |
| | HAVE 24" MIN. CLEAR HEIGHT OPENING. |
| | USE 35 SH WINDOW OR TALLERWINDOW TO |
| | MEET THE REQUIREMENTS OF SECTION |
| | 1005.4 SBC 1997. |
| | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH |
| | DOORS WITHOUT THE SIDELITES AS SHOWN |
| | ON ARCHITECTURAL PLANS. |
| | 4-TRUSS DRAWINGS: |
| | A)ARCHITECT TO REVIEW ALL TRUSS DRAWINGS |
| | PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | USE THE STANDARD REVIEW STAMP. |
| | B)ENGINEER TO SIGNS, SEAL & DATE TRUSS |
| | LAYOUT. CHAPTER 471 OF FL. STATUTES. |
| | C)ENGINEER TO UPDATE ALL GENERAL TRUSS |
| | DRAWINGS & PROVIDE ORIGINAL SIGNATURE |
| | AND DATE AS PER CHAPTER 471 FL. ST. |
| | SEE COMMENTS ON DRAWINGS. |
| | D)ENGINEER TO COORDINATE MEAN ROOF HT. |
| | WITH ARCHITECTURAL DRAWINGS. |
| | ALSO, THERE IS ONLY ONE MEAN ROOF HT |
| | FOR ENTIRE BUILDING. TRUSSES GE-1 AND |
| | T1 HAVE DIFFERENT MEAN ROOF HEIGHT. |
| | TABLE 1606.2A SBC 1997. |
| | MEAN ROOF HEIGHT GIVEN FOR TRUSS GE-1 |
| | IS INCORRECT. |
| | E)MISSING ENGINEERED TRUSSES HV-1, HV-2, |
| | V-3, V-4. |