2001-11-09 00:00:00APPROVED WITH PROVISO:
 1-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM:
 -MEAN ROOF HEIGHT AND BASIC VELOCITY
 PRESSURE DON'T MATCH. SEETABLE
 1606.2A SBC 1997.
 2-MASTER BEDROOM 34 SH WINDOW DOESN'T
 HAVE 24" MIN. CLEAR HEIGHT OPENING.
 USE 35 SH WINDOW OR TALLERWINDOW TO
 MEET THE REQUIREMENTS OF SECTION
 1005.4 SBC 1997.
 3-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITHOUT THE SIDELITES AS SHOWN
 ON ARCHITECTURAL PLANS.
 4-TRUSS DRAWINGS:
 A)ARCHITECT TO REVIEW ALL TRUSS DRAWINGS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 USE THE STANDARD REVIEW STAMP.
 B)ENGINEER TO SIGNS, SEAL & DATE TRUSS
 LAYOUT. CHAPTER 471 OF FL. STATUTES.
 C)ENGINEER TO UPDATE ALL GENERAL TRUSS
 DRAWINGS & PROVIDE ORIGINAL SIGNATURE
 AND DATE AS PER CHAPTER 471 FL. ST.
 SEE COMMENTS ON DRAWINGS.
 D)ENGINEER TO COORDINATE MEAN ROOF HT.
 WITH ARCHITECTURAL DRAWINGS.
 ALSO, THERE IS ONLY ONE MEAN ROOF HT
 FOR ENTIRE BUILDING. TRUSSES GE-1 AND
 T1 HAVE DIFFERENT MEAN ROOF HEIGHT.
 TABLE 1606.2A SBC 1997.
 MEAN ROOF HEIGHT GIVEN FOR TRUSS GE-1
 IS INCORRECT.
 E)MISSING ENGINEERED TRUSSES HV-1, HV-2,
 V-3, V-4.