Plan Review Notes
Plan Review Notes For Permit 01100954
Permit Number 01100954
Review Stop R
Sequence Number 1
Notes
Date Text
2001-10-31 00:00:00CHECKLIST:
 1-NEED TO RECORD NOTICE OF COMMENCEMENT
 WITH THE COURTHOUSE.
 2-AFTER CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS, TAKE THEM TO THE PALM BEACH
 COUNTY BUILDING TO PAY IMPACT FEES.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 3-ARCHITECT TO COMPLETELY FILL OUT THE
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM (ATTACHED).
 4-ARCHITECT TO SPECIFY THE DESIGN
 PRESSURES CALCULATED FOR ALL EXTERIOR
 OPENINGS AS REQUIRED BY SECTION 1606
 OF SBC 1997 (CLADDING & COMPONENTS).
 5-SINGLE HUNG WINDOWS 24 DON'T COMPLY W/
 EGRESS REQUIREMENTS SEC. 1005.4 SBC/97
 MINIMUM CLEAR HEIGHT TO BE 24".
 6-NEED 2 COPIES OF PRODUCT APPROVALS FOR
 A)ROOF SINGLES. B)SINGLE HUNG WINDOWS.
 C)WINDOW MULLIONS AND D)EXTERIOR FRENCH
 DOORS.
 7-PROVIDE COMPLETE TYPICAL WALL SECTION
 SPECIFYING:
 A)VAPOR BARRIER: SEC. 1909.2 SBC 1997.
 B)SOIL BEARING CAPACITY ASSUMED FOR THIS
 DESIGN. SEC. 104.2.2 CITY AMENDMENTS.
 C)FOOTING TO HAVE MIN. 12" BELOW FINISH
 GRADE. SEC. 1804.1.3 SBC 1997.
 D)SPECIFY SIZE OF ATTIC VENTS THAT
 COMPLY W/ SEC. 2309.7 SBC 1997.
 E)SPECIFY FIREBLOCKING. SEC. 2305 SBC/97
 8-ARCHITECT TO DATE DRAWINGS AT TIME OF
 SEALING THEM AS REQUIRED BY CHAPTER
 481 OF FLORIDA STATUTES WHEN SUBMITT'G
 DOCUMENTS FOR PUBLIC RECORDS.
 9-PROVIDE 2 COPIES OF PRODUCT APPROVAL
 FOR STORM PANELS AND COMPLETE INSTALL-
 ATION SCHEDULE, AS PER CITY SAMPLE
 ATTACHED COPY.
 A)ARCHITECT TO CLARIFY GENERAL NOTE
 #3: SHATTER PROOF GLASS AND MISSILE
 IMPACT GLAZING ARE DIFFERENT THINGS.
 CLARIFY IF THE INTENTION IS TO SPECIFY
 MISSILE IMPACT GLAZING FOR HURRICANE
 PROTECTION. IF SO, THEN PROVIDE THE
 REQUIRED PRODUCT APPROVALS.
 B)IF USING STORM SHUTTERS, ARCHITECT TO
 SPECIFY HOW ARE THE OPENINGS REINFORCED
 TO RECEIVE THE INSTALLATION OF THEM.
 10-WHERE IS THE ENGINEER'S SURVEY
 MENTIONED ON SITE PLAN.
 11-PROVIDE ROOF FRAMING PLAN INDICATING:
 A)ROOF SHEATHING FASTENING: TYPE, SIZE &
 SPACING. TABLE 2306.1 CITY AMENDMENTS
 TO SBC 1997 INCLUDING GABLE END ZONE.
 B)UPLIFT LOADS CALCULATED AND HURRICANE
 ANCHOR SCHEDULE.
 12-SPECIFY ATTACHMENT OF NEW CONSTRUCT'N
 TO EXISTING. INCLUDING ROOF, WALL AND
 CONCRETE SLAB AND FOOTING. SEC. 104.2.2
 OF CITY AMENDMENTS TO SBC 1997.
 13-PROVIDE ATTIC ACCESS. SEC 2309.6 SBC
 14-PROVIDE COMPLETE STRUCTURAL BUCK
 DETAIL FOR DOORS AND WINDOWS. SEC.
 1606 SBC/97 FOR CLADDING & COMPONENTS.
 15-PROVIDE ENERGY CALCULATIONS AS REQ'D
 BY FL. ENERGY CODE 1997 EDITION.
 16-SPECIFY NAILING OF TRUSS ANCHOR TA24
 BY HUGHES THAT WILL RESIST THE UPLIFT
 LOADS CALCULATED.
 17-PROVIDE COMPLETE GABLE END WALL SEC.
 SHOWING ALL STRUCTURAL COMPONENTS.
 -CLARIFY IF HAVING A RAKE TIE BEAM OR
 KNEE WALL ABOVE THE TIE BEAM.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 18-SPECIFY TIE BEAM AND LINTELS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
  
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DRAWING
 IN ORDER TO EXPEDITE THE REVIEW PROCESS.