| Plan Review Notes For Permit 01100954 |
| Permit Number |
01100954 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | **************** UNSAT *************** | | | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3)NOTE: PLEASE NOTE, PLANS NEED TO SHOW | | | LOAD CALCULATIONS, AND EXISTING SERVICE | | | SIZE. PLEASE INCLUDE ALL NEW LOAD AND | | | ITEMS ASKED FOR NOTE #2. PLEASE SEE. | | | 220-3-C-1 | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | BEDROOM | | | | | | 5) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | REAR. | | | | | | 6)NOTE: PLEASE CALRIFY IF THERE IS | | | GOING TO BE ANY NEW A/C EQUIPMNET? IF | | | SO , PLEASE INCLUDE UNIT ON PLANS W/ | | | REQ`D DISC AND RECEPT. 440-11/309.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|