2001-10-22 00:00:00**************** UNSAT ***************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE, PLANS NEED TO SHOW
 LOAD CALCULATIONS, AND EXISTING SERVICE
 SIZE. PLEASE INCLUDE ALL NEW LOAD AND
 ITEMS ASKED FOR NOTE #2. PLEASE SEE.
 220-3-C-1
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 BEDROOM
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 REAR.
  
 6)NOTE: PLEASE CALRIFY IF THERE IS
 GOING TO BE ANY NEW A/C EQUIPMNET? IF
 SO , PLEASE INCLUDE UNIT ON PLANS W/
 REQ`D DISC AND RECEPT. 440-11/309.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  