| 2001-11-02 00:00:00 | DENIED |
| | REFERENCES: SPC-94 - FACBC-97 |
| | |
| | 1) COVER SHEET NOTES SHOW (2),(5) & (6) |
| | AS COMFORT STATIONS. NO RESTROOM SHOWN |
| | FOR (2) OR (6), BUT NOTE THERE IS WATER |
| | AND SEWER RUN TO THESE COMFORT STATIONS. |
| | PLEASE CLAIRFY. |
| | 2) COMFORT STATION (5) NOT SHOWN ON PAGE |
| | 1 AS INDICATED ON COVER SHEET. PLEASE |
| | INDICATE WHAT SHEET THIS STATION WILL BE |
| | SHOWN ON. |
| | 3) PAGE A-1, FLOOR PLAN. RESTROOMS ARE |
| | NOT LARGE ENOUGH FOR 5' TURNING RADIUS |
| | REQUIRED PER FACBC SEC 4.22.3 & 4.2.3 |
| | MINIMUM DEPTH OF TOILET ROOM TO BE 7'5" |
| | 4) PAGE A-1 HDCP W/C TO COMPLY WITH SEC |
| | 4.16 OF FACBC-97 PLEASE SHOW DETAILS. |
| | 5) PAGE A-1 HDCP LAV TO COMPLY WITH SEC |
| | 4.19 OF FACBC-97 PLEASE SHOW DETAILS. |
| | 6) PAGE A-1 HDCP DRINKING FOUNTAIN TO |
| | COMPLY WITH SEC 4.15 OF FACBC-97 PLEASE |
| | SHOW DETAILS. IF SINGLE DRINKING FOUNT- |
| | AIN IS USED, PROVISIONS SHALL BE PROVID- |
| | ED FOR THOSE WHO HAVE DIFFICULTY BENDING |
| | OR STOOPING PER SEC 4.1.3(10) FACBC-97 |
| | 7) PAGE A-2 WATER SUPPLY RISER DIAGRAM. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | PER MANUFACTURE INSTALLATION INSTRUCTION |
| | AND WH-PDI 201, CLOSE TO FIXTURES NOT ON |
| | HIGH UP AS SHOWN. THESE ARRESTORS DO NOT |
| | REQUIRE ACCESS PANELS. |
| | 8) PAGE A-2 SANITARY RISER DIAGRAM. TRAP |
| | PRIMERS ARE REQUIRED ON FLOOR DRAINS IN |
| | PUBLIC RESTROOMS PER SPC SEC 409.4.1.1 |
| | |
| | REVIEW BY KEN STEVENS |