2001-11-02 00:00:00DENIED
 REFERENCES: SPC-94 - FACBC-97
  
 1) COVER SHEET NOTES SHOW (2),(5) & (6)
 AS COMFORT STATIONS. NO RESTROOM SHOWN
 FOR (2) OR (6), BUT NOTE THERE IS WATER
 AND SEWER RUN TO THESE COMFORT STATIONS.
 PLEASE CLAIRFY.
 2) COMFORT STATION (5) NOT SHOWN ON PAGE
 1 AS INDICATED ON COVER SHEET. PLEASE
 INDICATE WHAT SHEET THIS STATION WILL BE
 SHOWN ON.
 3) PAGE A-1, FLOOR PLAN. RESTROOMS ARE
 NOT LARGE ENOUGH FOR 5' TURNING RADIUS
 REQUIRED PER FACBC SEC 4.22.3 & 4.2.3
 MINIMUM DEPTH OF TOILET ROOM TO BE 7'5"
 4) PAGE A-1 HDCP W/C TO COMPLY WITH SEC
 4.16 OF FACBC-97 PLEASE SHOW DETAILS.
 5) PAGE A-1 HDCP LAV TO COMPLY WITH SEC
 4.19 OF FACBC-97 PLEASE SHOW DETAILS.
 6) PAGE A-1 HDCP DRINKING FOUNTAIN TO
 COMPLY WITH SEC 4.15 OF FACBC-97 PLEASE
 SHOW DETAILS. IF SINGLE DRINKING FOUNT-
 AIN IS USED, PROVISIONS SHALL BE PROVID-
 ED FOR THOSE WHO HAVE DIFFICULTY BENDING
 OR STOOPING PER SEC 4.1.3(10) FACBC-97
 7) PAGE A-2 WATER SUPPLY RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 PER MANUFACTURE INSTALLATION INSTRUCTION
 AND WH-PDI 201, CLOSE TO FIXTURES NOT ON
 HIGH UP AS SHOWN. THESE ARRESTORS DO NOT
 REQUIRE ACCESS PANELS.
 8) PAGE A-2 SANITARY RISER DIAGRAM. TRAP
 PRIMERS ARE REQUIRED ON FLOOR DRAINS IN
 PUBLIC RESTROOMS PER SPC SEC 409.4.1.1
  
 REVIEW BY KEN STEVENS