2001-10-25 00:00:00******************** UNSAT *************
  
  
 1)NOTE: PLEASE NOTE THAT RISER SHOWS AN
 EQUIPMENT GOROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METER AND MAIN BKR
 PANEL? PLEASE NOTE THAT THIS IS
 PARALLELING THE NEUTRAL.
  
 2)NOTE: PLEASE NOTE THAT BLDG/FOOTER
 STEEL IS REQ`D TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250-50
  
 3)NOTE: PLEASE NOTE AND CLARIFY THE
 SWITCHING METHOD FOR LIGHTS IN BATHROOMS
 ?? PLEASE NOTE THAT PLANS SHOWS S3.
 NOTE THAT IF IN ONE BATH, THEN PERSON IN
 OTHER BATH CAN TURN LIGHTS OFF?
 PLEASE NOTE THAT THIS MAY BE A PROBLEM
 WITH SAFETY.
  
  
 4)NOTE: PLEASE NOTE THAT CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  