| Plan Review Notes For Permit 01100681 |
| Permit Number |
01100681 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-01-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01100681 | | | 217 BUTLER STREET | | | | | | 1)- CHANGE OF OCCUPANCY, THE CONTRACTOR | | | SHALL HAVE THE PLANS REVIEWED BY PALM | | | BEACH COUNTY TO ASERTAIN IF COUNTY | | | IMPACT FEES ARE TO BE ASSESSED. | | | | | | 2) SHEET A-3 INDICATES NEW WINDOWS AS | | | WELL AS STORM SHUTTERS PLEASE PROVIDE | | | PRODUCT ACCEPTANCE REPORTS, EITHER | | | SBCCI OR DADE COUNTY REPORTS ARE ACCEPT- | | | ABLE. | | | | | | 3) FL. ACCESSIBILITY CODE 4.13.6 | | | MANEUVERING AT DOORS, THE GROUND FLOOR | | | OFFICE BATH DOOR REQUIRES A MINIMUM OF | | | 12" ON THE LATCH PUSH SIDE OF THE DOOR. | | | | | | 4) IS THE AREA DIRECTLY IN FRONT OF THE | | | OFFICE DOOR IS THIS FLOOR LEVEL WITH | | | THE INTERIOR FLOOR OR IS THERE A STEP? | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X8412 |
|