Plan Review Notes
Plan Review Notes For Permit 01100681
Permit Number 01100681
Review Stop E
Sequence Number 2
Notes
Date Text
2001-11-28 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
 2)NOTE: PLEASE NOTE THE BATH(S) GFI
 CIRCUTI IS STILL SHOWN WITH SMOKE DETEC.
 PLEASE LIST PER 210-11-C-3 20A,#12
  
 3)NOTE: PLEASE NOTE THE LOAD CALCUALTION
 -S SUBMTTED DO NOT INCLUDE LOADS ON
 EXISTING 6 UNITS? PLEASE ALSO NOTE
 ALL CONTINUOUS LOADS STILL NEED TO BE
 SHOWN AT 125%.
  
 4)NOTE: PLEASE NOTE, NOTE # 4 SECOND
 FLOOR DOOR? WHERE DOES THIS GO?
 MEANS OF EGRESS LT FOR FIRST FLOOR DOOR.
 210-70
  
 5)NOTE: PLEASE NOTE THAT 8 1/2X 11`S
 SUBMITTED BY ARCH BEING SIGNED,DATED AND
 SEALED, MUST CONTAIN A TITLE BLOCK PER
 61G-14.004.
  
 6)NOTE: PLEASE CLARIFY PANEL SHOWN AS
 EXISTING,NEW, SUB PANEL? WHICH ONE?
 FOR PANEL FOR OFFICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372