| 2001-11-28 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | FROM FIRST REVIEW WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE NOTE THE BATH(S) GFI | | | CIRCUTI IS STILL SHOWN WITH SMOKE DETEC. | | | PLEASE LIST PER 210-11-C-3 20A,#12 | | | | | | 3)NOTE: PLEASE NOTE THE LOAD CALCUALTION | | | -S SUBMTTED DO NOT INCLUDE LOADS ON | | | EXISTING 6 UNITS? PLEASE ALSO NOTE | | | ALL CONTINUOUS LOADS STILL NEED TO BE | | | SHOWN AT 125%. | | | | | | 4)NOTE: PLEASE NOTE, NOTE # 4 SECOND | | | FLOOR DOOR? WHERE DOES THIS GO? | | | MEANS OF EGRESS LT FOR FIRST FLOOR DOOR. | | | 210-70 | | | | | | 5)NOTE: PLEASE NOTE THAT 8 1/2X 11`S | | | SUBMITTED BY ARCH BEING SIGNED,DATED AND | | | SEALED, MUST CONTAIN A TITLE BLOCK PER | | | 61G-14.004. | | | | | | 6)NOTE: PLEASE CLARIFY PANEL SHOWN AS | | | EXISTING,NEW, SUB PANEL? WHICH ONE? | | | FOR PANEL FOR OFFICE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|