| 2001-11-02 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) PAGE A-5 CONVERTED PLUMBING PLAN. |
| | PLEASE SPECIFY IF SANITARY PIPING WILL |
| | BE PVC OR CAST IRON. MUST BE ALL ONE OR |
| | THE OTHER FOR FIRE PENETRATION APPROVAL |
| | 2) PAGE A-5 PLUMBING RISER NOT TO CODE. |
| | 1ST W/C NOT VENTED PROPERLY AND KITCHEN |
| | FROM 2ND FLOOR TO DRAIN INTO BLDG DRAIN |
| | NOT BRANCH LINE. SPC SEC 914.1 - 911.4 |
| | 3) PLEASE SUBMIT A WATER RISER DIAGRAM |
| | 4) PAGE A-5 HDCP W/C DETAIL. W/C TO BE |
| | 1'6" TO C/L OFF WALL AND 17" TO 19" TO |
| | TOILET SEAT ABOVE FINISH FLOOR. PLEASE |
| | SHOW DETAIL. |
| | 5) PAGE A-5 PLUMBING NOTES #14. AIR |
| | CHAMBERS DO NOT WORK, AND IF INSTALLED |
| | SHAL COMPLY WITH SPC SEC 607.8.3 AND BE |
| | ACCESSIBLE AND RECHARGEABLE PER WH-PDI |
| | 201. WATER HAMMER ARRESTORS IF USED |
| | SHALL BE LOCATED AND SIZED PER MANUFACT- |
| | URE INSTALLATIION INSTRUCTIONS AND WH- |
| | PDI 201, CLOSE TO FIXTURE. |
| | 6) PAGE A-4, WATER HEATER SHALL COMPLY |
| | WITH MODEL COUNTYWIDE AMENDMENTS TO SPC |
| | SEC 507.8.1 (SAFETY PAN) AND SHALL HAVE |
| | A MINIMUM 1" PAN DRAIN. ALSO P/T RELIEF |
| | VALVE TO BE FULL SIZE. BOTH TO DRAIN TO |
| | AN OBSERVABLE POINT OUTSIDE THE BLDG. & |
| | SHALL BE TURNED DOWN WITHIN 6" OF GROUND |
| | LEVEL. SEC 507.6 |
| | |