Plan Review Notes
Plan Review Notes For Permit 01100681
Permit Number 01100681
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-02 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE A-5 CONVERTED PLUMBING PLAN.
 PLEASE SPECIFY IF SANITARY PIPING WILL
 BE PVC OR CAST IRON. MUST BE ALL ONE OR
 THE OTHER FOR FIRE PENETRATION APPROVAL
 2) PAGE A-5 PLUMBING RISER NOT TO CODE.
 1ST W/C NOT VENTED PROPERLY AND KITCHEN
 FROM 2ND FLOOR TO DRAIN INTO BLDG DRAIN
 NOT BRANCH LINE. SPC SEC 914.1 - 911.4
 3) PLEASE SUBMIT A WATER RISER DIAGRAM
 4) PAGE A-5 HDCP W/C DETAIL. W/C TO BE
 1'6" TO C/L OFF WALL AND 17" TO 19" TO
 TOILET SEAT ABOVE FINISH FLOOR. PLEASE
 SHOW DETAIL.
 5) PAGE A-5 PLUMBING NOTES #14. AIR
 CHAMBERS DO NOT WORK, AND IF INSTALLED
 SHAL COMPLY WITH SPC SEC 607.8.3 AND BE
 ACCESSIBLE AND RECHARGEABLE PER WH-PDI
 201. WATER HAMMER ARRESTORS IF USED
 SHALL BE LOCATED AND SIZED PER MANUFACT-
 URE INSTALLATIION INSTRUCTIONS AND WH-
 PDI 201, CLOSE TO FIXTURE.
 6) PAGE A-4, WATER HEATER SHALL COMPLY
 WITH MODEL COUNTYWIDE AMENDMENTS TO SPC
 SEC 507.8.1 (SAFETY PAN) AND SHALL HAVE
 A MINIMUM 1" PAN DRAIN. ALSO P/T RELIEF
 VALVE TO BE FULL SIZE. BOTH TO DRAIN TO
 AN OBSERVABLE POINT OUTSIDE THE BLDG. &
 SHALL BE TURNED DOWN WITHIN 6" OF GROUND
 LEVEL. SEC 507.6
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377