| Date |
Text |
| 2001-10-30 00:00:00 | ******************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THE LOAD |
| | CALCULATIONS FRO COMMERCIAL AREA NEEDS |
| | TO BE SHOWN. ALL CONTINUOUS LOADS AT |
| | 125%/ LARGEST MOTOR ETC. |
| | |
| | 3)NOTE: PLEASE SUBMIT AN ELECTRICAL |
| | RISER DIAGRAM SHOWING FEED TO NEW PANEL? |
| | FROM EXISTING? HOW IS EXISTING FED? |
| | CONDUCTOR SIZES, CONDUITS, GROUNDING |
| | 215-5/250-122/310-16 |
| | NOTES ON PLANS MENTION THAT ELECTRICAN |
| | IS SUBMIT ALL THIS INFORMATION THAT |
| | IS NEEDED. THIS IS REQ`D AT THIS TIME |
| | FOR PLAN REVIEW BY THE ARCH/ENGINEER |
| | OF RECORD. |
| | |
| | 4)NOTE: PLEASE CLARIFY DOOR SHOWN FROM |
| | SECOND FLOOR TO ?? MEANS OF EGRESS? |
| | 210-70 |
| | |
| | 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 6)NOTE: PLANS ONLY SHOW ONE SMALL APPL |
| | CIRCUIT? 210-52B |
| | |
| | 7)NOTE: PLEASE NOTE THAT ALL CIRCUIT #`S |
| | ARE TO BE SHOWN ON PLANS AND CORRELATE |
| | WITH SUBMITTED PANEL SCHEDULES. |
| | COMMERICAL AREA. |
| | |
| | 8)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT |
| | PER 600-5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |