2001-10-30 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS FRO COMMERCIAL AREA NEEDS
 TO BE SHOWN. ALL CONTINUOUS LOADS AT
 125%/ LARGEST MOTOR ETC.
  
 3)NOTE: PLEASE SUBMIT AN ELECTRICAL
 RISER DIAGRAM SHOWING FEED TO NEW PANEL?
 FROM EXISTING? HOW IS EXISTING FED?
 CONDUCTOR SIZES, CONDUITS, GROUNDING
 215-5/250-122/310-16
 NOTES ON PLANS MENTION THAT ELECTRICAN
 IS SUBMIT ALL THIS INFORMATION THAT
 IS NEEDED. THIS IS REQ`D AT THIS TIME
 FOR PLAN REVIEW BY THE ARCH/ENGINEER
 OF RECORD.
  
 4)NOTE: PLEASE CLARIFY DOOR SHOWN FROM
 SECOND FLOOR TO ?? MEANS OF EGRESS?
 210-70
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLANS ONLY SHOW ONE SMALL APPL
 CIRCUIT? 210-52B
  
 7)NOTE: PLEASE NOTE THAT ALL CIRCUIT #`S
 ARE TO BE SHOWN ON PLANS AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULES.
 COMMERICAL AREA.
  
 8)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT
 PER 600-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  