Plan Review Notes
Plan Review Notes For Permit 01100677
Permit Number 01100677
Review Stop M
Sequence Number 1
Notes
Date Text
2001-10-29 00:00:00*******************PROVISO**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.PLEASE NOTE DRYER EXHAUST BEING
 EXTENDED TO NEW EXTERIOR WALL SHALL
 COMPLY WITH 1997 SMC 509.3.THE
 MAXIMUM LENGTH SHALL NOT EXCEED 25'.
 THERE SHALL BE A DEDUCTION OF 2 1/2'
 FOR EACH 45 DEGREE BEND AND 5' FOR
 EACH 90 DEGREE BEND.TERMINATION
 SHALL BE LOCATED 10' FROM ANY
 ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW,
 DOOR OR AIR INTAKE.OPENING SHALL
 BE LOCATED AT LEAST 10' ABOVE THE
 ADJOINING GRADE LEVEL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.