| Plan Review Notes For Permit 01100677 |
| Permit Number |
01100677 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-29 00:00:00 | *******************PROVISO************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.PLEASE NOTE DRYER EXHAUST BEING | | | EXTENDED TO NEW EXTERIOR WALL SHALL | | | COMPLY WITH 1997 SMC 509.3.THE | | | MAXIMUM LENGTH SHALL NOT EXCEED 25'. | | | THERE SHALL BE A DEDUCTION OF 2 1/2' | | | FOR EACH 45 DEGREE BEND AND 5' FOR | | | EACH 90 DEGREE BEND.TERMINATION | | | SHALL BE LOCATED 10' FROM ANY | | | ADJACENT BUILDING, PARKING AREA, | | | ADJACENT PROPERTY LINE, WINDOW, | | | DOOR OR AIR INTAKE.OPENING SHALL | | | BE LOCATED AT LEAST 10' ABOVE THE | | | ADJOINING GRADE LEVEL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|