| 2001-10-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01100677 |
| | 1041 45TH ST |
| | CONT: CATALFUMO |
| | TEL: 624-9697X256 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- SQ.FT. OF EXISTING BUILDING, SQ.FT |
| | OF NEW ADDITION? IS THE ENTIRE BLDG |
| | FIRE SPRIKLERED? |
| | |
| | 2)- MINIMUM BUILD. TYPE? |
| | |
| | 3) SBC TABLE 500, INSTITUTIONAL,OR |
| | RESTRAIED OR UNRESTRAINED? |
| | |
| | 4)- SH-1 INDICATES SOILS REPORT TO |
| | BE COMPLETED? |
| | |
| | 5)- PLANS ARE UNCLEAR AS TO AREAS OF |
| | WORK OTHER THAN ADDITION? |
| | |
| | 6)- SHEET 34 DETAIL #1: |
| | A) 12"X12" BLOCK COLUMN W/4 #5 REBAR, |
| | ARE HOOPS REQUIRED? ACI 530-95 5.9 |
| | B) 12"X12" BLOCK COLUMN, MISSING INFO |
| | FOR THE EMBED PLATE TOP OF COLUMN? |
| | THICKNESS,SIZE, EMBED STUD SIZE & |
| | COUNTOR WELD SIZE, TYPE TO W8X14. |
| | C) 12"-0" BEAM NO STIRRUPS OR HOOPS? |
| | |
| | 7)- SHEET 4 DETAILS 1,2&3 INDICATE A 8" |
| | HIGH PARAPET AROUND THE ROOF DECK, ROOF |
| | DRAINAGE? SCUPPERS & OVERFLOWS SEE |
| | SBC 1517.6.4.3. |
| | |
| | 8)- ROOF DETAILS INDICATE A P.T. 2X_ |
| | AROUND THE EDGE OF THE ROOF NO INFO FOR |
| | ATTACHMENT TO CONCRETE BM OR METAL DECK. |
| | |
| | 9)- SBC 1606.2.6.2COMPONENTS & CLADDING |
| | MISSING PRODUCT APPROVAL REPORTS (2COP- |
| | IES) REQUIRED FOR: |
| | WINDOWS |
| | DOORS |
| | DOORS/SIDELITES/TRANSOM (TEST ASSEMBLY) |
| | ROOFING |
| | STORM SHUTTERS,SEE ATTACHMENT SCHEDULE |
| | |
| | 10)- SBC TABLE 803.3 MIMIMUM INTERIOR |
| | FINISH SCHEDULE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096X8412 |