Plan Review Notes
Plan Review Notes For Permit 01100606
Permit Number 01100606
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-10-25 00:00:001) NO SMOKE DETECTORS OBSERVED IN
 RESIDENTIAL UNITS. ELECTRIC POWERED
 SMOKE DETECTORS ARE REQUIRED.
 2) RESIDENTIAL UNIT DOORS TO BE AT
 LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES.
 3) RESIDENTIAL UNITS ARE TO BE SEPARATED
 FROM ONE ANOTHER BY AT LEAST ONE HOUR.
 4) PLEASE INDICATE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILINGS.
 5) EXIT DISCHARGE LOCATIONS NEAR AIR
 HANDLING UNITS DOES NOT MEET
 MINIMUM CODE REQUIREMENTS.
 6) BOTH EXITS FROM WORK AREA 108 ARE
 NOT PROPERLY SEPARATED FROM ONE ANOTHER
 BY AT LEAST 1/2 THE DIAGONAL DISTANCE.
 7) FABRIC AWNINGS TO BE FIRE RETARDANT
 MATERIAL.
 8) WINDOWS NOTED WITHIN 10 FEET OF
 STAIRS, PLEASE EXPLAIN PROTECTION.
 9) ARE THE CLOSETS SHOWN ON THE
 STAIRS FLOOR PLAN LOCATED UNDERNEATH
 THE STAIRS. IF SO WHAT IS THE
 FIRE RATING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910