| Plan Review Notes For Permit 01100606 |
| Permit Number |
01100606 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-25 00:00:00 | 1) NO SMOKE DETECTORS OBSERVED IN | | | RESIDENTIAL UNITS. ELECTRIC POWERED | | | SMOKE DETECTORS ARE REQUIRED. | | | 2) RESIDENTIAL UNIT DOORS TO BE AT | | | LEAST 20 MINUTE FIRE RATED AND BE | | | EQUIPPED WITH SELF-CLOSING DEVICES. | | | 3) RESIDENTIAL UNITS ARE TO BE SEPARATED | | | FROM ONE ANOTHER BY AT LEAST ONE HOUR. | | | 4) PLEASE INDICATE INTERIOR FINISH | | | INFORMATION FOR WALLS AND CEILINGS. | | | 5) EXIT DISCHARGE LOCATIONS NEAR AIR | | | HANDLING UNITS DOES NOT MEET | | | MINIMUM CODE REQUIREMENTS. | | | 6) BOTH EXITS FROM WORK AREA 108 ARE | | | NOT PROPERLY SEPARATED FROM ONE ANOTHER | | | BY AT LEAST 1/2 THE DIAGONAL DISTANCE. | | | 7) FABRIC AWNINGS TO BE FIRE RETARDANT | | | MATERIAL. | | | 8) WINDOWS NOTED WITHIN 10 FEET OF | | | STAIRS, PLEASE EXPLAIN PROTECTION. | | | 9) ARE THE CLOSETS SHOWN ON THE | | | STAIRS FLOOR PLAN LOCATED UNDERNEATH | | | THE STAIRS. IF SO WHAT IS THE | | | FIRE RATING. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|