| 2001-11-05 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT THE SEOCND |
| | SERVICE (METER BANK #2 ) NEEDS TO HAVE |
| | MAINS LABELED AS MAINS 1-5. PLEASE NOTE |
| | THAT THIS IS A SEPARATE SERVICE FROM |
| | THE OTHER BLDG (METER 1). |
| | |
| | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | WITH CIRCUIT #`S ON PLANS. |
| | PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3)NOTE: PLEASE NOTE BATH GFI FOR PANEL |
| | "F" APT SHOW BATH GFI ON CIRCUIT #13 |
| | W/ OTHER OUTLETS? PLEASE CORRECT. |
| | 210-11-C-3. |
| | |
| | 4)NOTE: PLEASE NOTE EGRESS LIGHTING FOR |
| | BEDROOMS, SHOWN AS FANS?? CLARIFY IF |
| | THEY ARE FAN/LT KITS? PLEASE SHOW. |
| | |
| | 5)NOTE: PLEASE NOTE LOCATION OF WATER |
| | HEATER UNDER CABINET IN KITCHEN DOES NOT |
| | SEEM TO MEET ACCESS OR CLEARENCE CODES |
| | FOR HEATING APPLIANCES OR DISCONNECTING |
| | MEANS. 110-26 PLEASE CLARIFY WATER |
| | HEATER SHOWN IN CORNER? DOORS CABINET |
| | WALLS? |
| | |
| | 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 7)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | APT "C" BEDROOM WALL. 210-52 2' OF |
| | WALL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |