Plan Review Notes
Plan Review Notes For Permit 01100606
Permit Number 01100606
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-05 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE SEOCND
 SERVICE (METER BANK #2 ) NEEDS TO HAVE
 MAINS LABELED AS MAINS 1-5. PLEASE NOTE
 THAT THIS IS A SEPARATE SERVICE FROM
 THE OTHER BLDG (METER 1).
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 WITH CIRCUIT #`S ON PLANS.
 PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE BATH GFI FOR PANEL
 "F" APT SHOW BATH GFI ON CIRCUIT #13
 W/ OTHER OUTLETS? PLEASE CORRECT.
 210-11-C-3.
  
 4)NOTE: PLEASE NOTE EGRESS LIGHTING FOR
 BEDROOMS, SHOWN AS FANS?? CLARIFY IF
 THEY ARE FAN/LT KITS? PLEASE SHOW.
  
 5)NOTE: PLEASE NOTE LOCATION OF WATER
 HEATER UNDER CABINET IN KITCHEN DOES NOT
 SEEM TO MEET ACCESS OR CLEARENCE CODES
 FOR HEATING APPLIANCES OR DISCONNECTING
 MEANS. 110-26 PLEASE CLARIFY WATER
 HEATER SHOWN IN CORNER? DOORS CABINET
 WALLS?
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 7)NOTE: PLEASE NOTE MISSING OUTLET FOR
 APT "C" BEDROOM WALL. 210-52 2' OF
 WALL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372