| Plan Review Notes For Permit 01100593 |
| Permit Number |
01100593 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-02 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW # 01100593 | | | 700 S ROSEMARY AV | | | KIOSK- RESTRAUNT | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- KIOSK PLANS ARE OF A CONCEPTUAL | | | NATURE ONLY. THERE IS NO INTERIOR | | | DETAIL INFORMATION, WILL THE PUBLIC SIT | | | INSIDE? | | | 2) DISCREPANCIES: SHEET A-2 INDICATES A | | | STRUCTURE WITH EXTERIOR GLAZING, VS A-3 | | | WHICH INDICATES A MORE OPEN AIR STRUC- | | | TURE? | | | INDICATE THE TYPE OF STRUCTURE, ENCLOSED | | | PARTIALLY OR OPEN. USE SBC TABLE | | | 1606.2B TO FIND THE COEFICIENTS TO BE | | | USED TO FIND WIND PRESURE ZONES. PROVIDE | | | CALCS. | | | 3)- MISSING IS THE PRODUCT TESTING FOR | | | WINDOWS, DOORS, ROOFING & STORM SHUTTERS | | | PLANS DEPICT A TRIFOLD STORM SHUTTER, | | | PROVIDE PRODUCT TESTING FOR THIS TYPE OF | | | APPLICATION. | | | 4)- COLUMN DETAIL DOESN'T GIVE DETAIL AS | | | TO FASTENING OF THE WOOD BEAMS? | | | 5)- PLANS ARE TO GO TO COUNTY FOR IMPACT | | | FEES. | | | 6)- PLANS ARE INADEQUATE TO DO A | | | THOROUGH PLAN REVIEW. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096X8412 |
|