| Plan Review Notes For Permit 01100589 |
| Permit Number |
01100589 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-30 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01100589 | | | 777 S FLAGLER /1102 7TH FL/12 FL | | | CATALFUMO | | | 624-9697X256 | | | | | | 1)- ADDITIONAL INFO REQUIRED, THE LOCA- | | | TION OF THE REFIGERANT PIPING THROUGH | | | THE VARIOUS FLOORS? EXAMPLE, IS THIS LO- | | | CATED IN A STAIRWELL, COMMON AREAS OR | | | TENANT SPACES. | | | | | | 2)- THE PLANS DEPICT THE REFRIGARANT PIP | | | ING TO BE INSULATED WITH 3/4 " ARMAFLEX. | | | SBC 705.4.3 INSULATION AND COVERINGS ON | | | THE PENETRATING ITEM SHALL NOT PENETRATE | | | THE ASSEMBLY UNLESS THE SPECIFIC MATER- | | | IAL USED HAS BEEN TESTED AS PART OF THE | | | ASSEMBLY IN ACCORDANCE WITH 705.6 | | | | | | 3)- SBC705.6 ALL PENETRATIONS OF A FLOOR | | | FLOOR/ CEILING ASSEMBLY OR THE CEILING | | | MEMBER OF A ROOF/CEILING ASSEMBLY SHALL | | | BE IN ACCORDANCE WITH 705.2.PROVIDE | | | MANUFACTURES SPEC ON THE FIRE STOPPING | | | MATERIAL AND THE RATING.TABLE 600 / | | | TYPE I BUILD. 2 HR FLOOR RATING/SPRINK- | | | LERED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|