| Plan Review Notes For Permit 01100537 |
| Permit Number |
01100537 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | 1) WHY IS THERE NO MANUAL PULL STATION | | | SHOWN NEAR THE STAIRWAY. IS THERE AN | | | EXISTING ONE? | | | 2) NO HORN STROBES SHOWN IN THE AREA | | | OF THE MEDITATION, SALON, WAITING, OR | | | MEDITATION AREAS. | | | 3) A SMOKE DETECTOR IS SHOWN IN THE | | | LAUNDRY ROOM. A HEAT DETECTOR WOULD | | | BETTER SERVE THIS LOCATION. | | | 4) WHY IS THERE NO SMOKE DETECTOR | | | SHOWN AT THE ELEVATOR AREA. IS THERE | | | AN EXISTING ONE? | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|