| Plan Review Notes For Permit 01100477 |
| Permit Number |
01100477 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | *******************PROVISO************** | | | | | | | | | PROVISO FROM NANCY DENMARKS REVIEW OF | | | MASTER PERMIT 01091067, NOTES ON PERMIT | | | 01091067. | | | | | | ALL COPPER CONDENSER WATER PIPING TO BE | | | BRAZED PER 1997 SMC TABLE 1205. | | | | | | FIELD VERIFICATION OF FIRE DAMPERS AT | | | ALL RATED WALL PENETRATIONS BY DUCTS | | | REQUIRED. | | | | | | NO COMBUSTIBLE MATERIALS, INCLUDING PVC | | | ALLOWED IN THE RETURN AIR PLENUM AREA | | | ABOVE THE CEILING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|