Plan Review Notes
Plan Review Notes For Permit 01100410
Permit Number 01100410
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-18 00:00:00*********** UNSAT *********************
  
 1)NOTE: PLEASE NOTE THAT PLANS DO NOT
 INCLUDE THE HEAT PUMP IN THE WIRING
 DIAGRAM? PLEASE SHOW W/ WIRE/CONDUIT
 SIZES ETC.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 WITH ALL NEW LOADS ADDED AND ALSO
 INCLUDE SIZE OF EXISTING SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372