2001-10-29 00:00:00DENIED
 REFERENCE SPC-94
  
 1) PAGE MP-1, WATER RISER DIAGRAM.
 AIR CHAMBERS ARE "QUICK FIX" AND NEED TO
 BE ACCESSIBLE AND RECHARGEABLE PER WH-
 PDI 201. WATER HAMMER ARRESTORS SHALL BE
 INSTALLED PER MANUFACTURES INSTALLATION
 INSTRUCTIONS AND WH-PDI 201, DOWN CLOSE
 TO FIXTURES NOT AT TOP OF DROP AS SHOWN.
 PLEASE SUBMIT RISER DIAGRAM SHOWING
 THIS FOR PLAN REVIEW.
  