| Plan Review Notes For Permit 01100405 |
| Permit Number |
01100405 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-29 00:00:00 | DENIED | | | REFERENCE SPC-94 | | | | | | 1) PAGE MP-1, WATER RISER DIAGRAM. | | | AIR CHAMBERS ARE "QUICK FIX" AND NEED TO | | | BE ACCESSIBLE AND RECHARGEABLE PER WH- | | | PDI 201. WATER HAMMER ARRESTORS SHALL BE | | | INSTALLED PER MANUFACTURES INSTALLATION | | | INSTRUCTIONS AND WH-PDI 201, DOWN CLOSE | | | TO FIXTURES NOT AT TOP OF DROP AS SHOWN. | | | PLEASE SUBMIT RISER DIAGRAM SHOWING | | | THIS FOR PLAN REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 569-8096 EXT 8377 |
|