2001-10-16 00:00:00PROVISO:
 1. OUTSIDE AIR BALANCE CONFLICTS W/ THE
 ASHRAE CALCULATIONS. ASHRAE REQUIRED 210
 CFM OF OUTSIDE AIR IS REQUIRED.
 2. LOCATE AHU WITH RESPECT TO BUILDING C
 ONSTRUCTION TO ALLOW FOR SERVICE AND REP
 LACEMENT PER SMC 304.2