| Plan Review Notes For Permit 01100405 |
| Permit Number |
01100405 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-16 00:00:00 | PROVISO: | | | 1. OUTSIDE AIR BALANCE CONFLICTS W/ THE | | | ASHRAE CALCULATIONS. ASHRAE REQUIRED 210 | | | CFM OF OUTSIDE AIR IS REQUIRED. | | | 2. LOCATE AHU WITH RESPECT TO BUILDING C | | | ONSTRUCTION TO ALLOW FOR SERVICE AND REP | | | LACEMENT PER SMC 304.2 |
|