| 2001-10-09 00:00:00 | 1) PLEASE INDICATE ON PLANS WHERE THE | | | NEAREST FIRE HYDRANT IS LOCATED TO | | | THE DOCKS. | | | 2) PLEASE INDICATE HOW THE STANDPIPE | | | WILL BE SUPPORTED TO THE DOCKS. | | | 3) ARE ANY CONNECTIONS PRESENT TO SUPPLY | | | THE STANDPIPE SYSTEM. | | | 4) THE STANDPIPE SYSTEM WET OR DRY. | | | 5) PLEASE PROVIDE DETAIL ON STANDPIPE | | | HOSE VALVES. | | | 6) PLANS DO NOT INDICATE PRESSURE | | | TESTING OF PIPING. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|