 PROVISO:
  
 RTU-3 & RTU-1, DUCTS APPEAR TO BE
 PENETRATING NEW 2 HR RATED WALL.FIRE
 DAMPERS ARE REQUIRED IN WALLS HAVING A
 FIRE RESISTANCE RATING OF 1 OR MORE
 HOURS.
  
 FIRE DAMPERS SHALL COMPLY WITH UL 555 &
 SHALL BEAR THE LABLE OF AN APPROVED
 TESTING AGENCY.
  
 PROVIDE LOCATION AND INSTALLATION
 DETAILS OF THE DAMPERS PRIOR TO
 INSPECTION.
  