| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-02-21 00:00:00 | | | | PROVISO: | | | | | | RTU-3 & RTU-1, DUCTS APPEAR TO BE | | | PENETRATING NEW 2 HR RATED WALL.FIRE | | | DAMPERS ARE REQUIRED IN WALLS HAVING A | | | FIRE RESISTANCE RATING OF 1 OR MORE | | | HOURS. | | | | | | FIRE DAMPERS SHALL COMPLY WITH UL 555 & | | | SHALL BEAR THE LABLE OF AN APPROVED | | | TESTING AGENCY. | | | | | | PROVIDE LOCATION AND INSTALLATION | | | DETAILS OF THE DAMPERS PRIOR TO | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|