| 2001-11-02 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 3) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. MISSLE |
| | IMPACT PROTECTION IS REQUIRED FOR ALL |
| | EXTERIOR GLAZED AREAS. SEE ATTACHED. |
| | |
| | 4) WHERE LATH AND STUCCO FINISH IS |
| | APPLIED OVER THE EXTERIOR OF WOOD FRAME |
| | CONSTRUCTION, AN APPROVED WEEP SCREED |
| | (STUCCO STOP) PLACED NOT LESS THAN |
| | 6 INCHES ABOVE FINISHED GRADE SHALL BE |
| | USED TO TERMINATE THE STUCCO AT THE BASE |
| | OF THE WALL. SECTION 2304.2.5 OF THE |
| | CITY OF WPB AMENDMENTS TO THE 97 SBC. |
| | PLANS INDICATE 5 INCHES.PLEASE CORRECT. |
| | |
| | 5) THE GLAZING IN THE WINDOWS WITHIN A |
| | 24 INCH RADIUS OF A DOOR IN THE CLOSED |
| | POSITION ARE REQUIRED TO BE SAFETY GLASS |
| | PER SECTION 2405.2.1 OF THE 97 SBC. |
| | PLEASE INDICATE THIS ON THE PLANS. |
| | |
| | 6) ONE OF THE WINDOWS IS SHOWN AS BEING |
| | LOCATED CLOSER TO THE DOOR ON THE NORTH |
| | ELEVATION THAN ON THE FLOOR PLAN. PLEASE |
| | CLARIFY. |
| | |
| | 7) STUCCO IS REQUIRED TO BE 7/8" THICK |
| | WHEN APPLIED OVER WIRE LATHE PER SEC. |
| | 2504.2 OF 97 SBC AND ASTM C 926. |
| | |
| | 8)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - FIXED GLASS WINDOWS |
| | |
| | 9) INDICATE THE TYPE OF ROOM IN EXISTING |
| | RESIDENCE THAT WINDOWS ARE BEING BLOCKED |
| | OFF. IF IN A BEDROOM, EMERGENCY EGRESS |
| | MUST BE MAINTAINED AND IN A BATHROOM, A |
| | MECHANCIAL VENT MAY BE REQUIRED. |
| | |
| | 10) INDICATE THE SIZE, SPACING AND THE |
| | METHOD OF ATTACHMENT OF THE EXISTING |
| | ROOF RAFTERS/JOISTS. |
| | |
| | 11) PLEASE CLARIFY WALL SECTION ON A-2. |
| | HEADER IS SHOWN BETWEEN RAFTERS. |
| | INDICATE SIZE OF HEADERS OVER FIXED |
| | GLASS WINDOWS IN EXTERIOR BEARING WALL. |
| | |
| | 12) PROVIDE FLASHING DETAIL FOR ROOF AND |
| | WALL INTERSECTION BELOW FIXED GLASS |
| | WINDOWS. |
| | |
| | 13)CLARIFY ATTACHMENT METHOD AT EXISTING |
| | SRORAGE ROOM WALLS. THE EXISTING 4X4 |
| | APPEARS TO BE AGAINST THE CBS WALL. |
| | THE FLOOR PLAN AND ATTACHMENT METHOD |
| | INDICATE 2X4 EXTERIOR WALLS AND THE WALL |
| | SECTION INDICATES 2X6 WOOD FRAME |
| | EXTERIOR WALLS. PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |