Plan Review Notes
Plan Review Notes For Permit 01100340
Permit Number 01100340
Review Stop B
Sequence Number 1
Notes
Date Text
2001-11-02 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 3) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. MISSLE
 IMPACT PROTECTION IS REQUIRED FOR ALL
 EXTERIOR GLAZED AREAS. SEE ATTACHED.
  
 4) WHERE LATH AND STUCCO FINISH IS
 APPLIED OVER THE EXTERIOR OF WOOD FRAME
 CONSTRUCTION, AN APPROVED WEEP SCREED
 (STUCCO STOP) PLACED NOT LESS THAN
 6 INCHES ABOVE FINISHED GRADE SHALL BE
 USED TO TERMINATE THE STUCCO AT THE BASE
 OF THE WALL. SECTION 2304.2.5 OF THE
 CITY OF WPB AMENDMENTS TO THE 97 SBC.
 PLANS INDICATE 5 INCHES.PLEASE CORRECT.
  
 5) THE GLAZING IN THE WINDOWS WITHIN A
 24 INCH RADIUS OF A DOOR IN THE CLOSED
 POSITION ARE REQUIRED TO BE SAFETY GLASS
 PER SECTION 2405.2.1 OF THE 97 SBC.
 PLEASE INDICATE THIS ON THE PLANS.
  
 6) ONE OF THE WINDOWS IS SHOWN AS BEING
 LOCATED CLOSER TO THE DOOR ON THE NORTH
 ELEVATION THAN ON THE FLOOR PLAN. PLEASE
 CLARIFY.
  
 7) STUCCO IS REQUIRED TO BE 7/8" THICK
 WHEN APPLIED OVER WIRE LATHE PER SEC.
 2504.2 OF 97 SBC AND ASTM C 926.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FIXED GLASS WINDOWS
  
 9) INDICATE THE TYPE OF ROOM IN EXISTING
 RESIDENCE THAT WINDOWS ARE BEING BLOCKED
 OFF. IF IN A BEDROOM, EMERGENCY EGRESS
 MUST BE MAINTAINED AND IN A BATHROOM, A
 MECHANCIAL VENT MAY BE REQUIRED.
  
 10) INDICATE THE SIZE, SPACING AND THE
 METHOD OF ATTACHMENT OF THE EXISTING
 ROOF RAFTERS/JOISTS.
  
 11) PLEASE CLARIFY WALL SECTION ON A-2.
 HEADER IS SHOWN BETWEEN RAFTERS.
 INDICATE SIZE OF HEADERS OVER FIXED
 GLASS WINDOWS IN EXTERIOR BEARING WALL.
  
 12) PROVIDE FLASHING DETAIL FOR ROOF AND
 WALL INTERSECTION BELOW FIXED GLASS
 WINDOWS.
  
 13)CLARIFY ATTACHMENT METHOD AT EXISTING
 SRORAGE ROOM WALLS. THE EXISTING 4X4
 APPEARS TO BE AGAINST THE CBS WALL.
 THE FLOOR PLAN AND ATTACHMENT METHOD
 INDICATE 2X4 EXTERIOR WALLS AND THE WALL
 SECTION INDICATES 2X6 WOOD FRAME
 EXTERIOR WALLS. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202