| Plan Review Notes For Permit 01100285 |
| Permit Number |
01100285 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-21 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | (1) SHT A1,MINIMUM FACILITIES, TAB 407 | | | REQUIRES 3 W/C'S AND 3 LAVS, IN RM 210 | | | WOMENS REST RM. | | | (2)SHT A-1-5, BREAK SINK, RM 219, COMPLY | | | WITH FACBC-97 SEC 4.24, HGTH 34" AFF. | | | (3)SHT P1 SPECIFICATIONS, LIST MATERIALS | | | FOR DWV AND WATER PIPING, SEC 104.2 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|