| Plan Review Notes For Permit 01100285 |
| Permit Number |
01100285 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-24 00:00:00 | ******************* UNSAT *********** | | | | | | 1)NOTE: PLEASE CLARIFY OCP FOR "EXISTING | | | "DS-2 FEEDING NEW '2M'. PLEASE NOTE | | | PLANS DO NOT SHOW SIZE. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%. PLEASE NOTE THAT LOADS ARE SHOWN | | | AT CONNECTED/AMPS/DEMAND? NEED TO SHOW | | | WATTS/SQ FT/OUTLETS LOADS. ?= 180VA. | | | PLEASE NOTE THAT LOAD SHOWN FOR OUTELTS | | | IS AT 13.1KW, PLEASE NOTE BY ROUGH | | | COUNT IT APPEARS TO BE HIGHER? | | | PLEASE CLARIFY BY SHOWING. | | | LARGEST MOTOR AT 125% ALSO. | | | 215-5. 215-2,230-42,,,,, | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW, IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|