2001-11-08 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) ATTIC ACCESS OPENING IS REQUIRED TO
 BE NOT LESS THAN 22X36 INCHES PER 97 SBC
 SEC. 2309.6. PLEASE CORRECT.
  
 3) THE LETTER FROM THE SOIL ENGINEER
 STATES THAT THE FOUNDATIONS BEAR 14-
 INCHES BELOW FINAL GRADE. THE CITY OF
 WPB AMENDMENTS TO THE 97 SBC REQUIRE THE
 BUILDING FLOOR ELEVATION AT THE
 PERIMETER OF MONOLITHIC FOUNDATIONS TO
 BE A MINIMUM OF 4" ABOVE FINISH GRADE AT
 HABITABLE AREAS. THEREFORE, THE FOOTING
 IS REQUIRED TO BE 18" IN DEPTH. THE
 PLANS INDICATE 16" DEEP FOOTINGS. PLEASE
 CORRECT.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR
 THE SINGLE HUNG WINDOWS (+42,-55 PSF) DO
 NOT MEET THE WINDLOAD REQUIREMENTS FOR
 THE (2) 1/2 36 SH WINDOWS(+43,-58 PSF).
 PLEASE CORRECT.
  
 TRUSSES
  
 1) THE TRUSS DESIGN CERTIFICATION COVER
 SHEET DESIGNATES WINDLOADS IN COMPLIANCE
 WITH ASCE 7-95 FOR 150 MPH. HOWEVER,
 SOME OF THE TRUSS DRAWINGS INDICATE
 110 MPH WINDLOADS & 12 FT. WALL HEIGHT
 AND OTHERS 150 MPH & 24 FT. WALL HEIGHT.
 THE STRUCTURE IS DESIGNED TO ASCE 7-95
 AND 145 MPH PER SHEET S1. PLEASE
 CORRECT.
  
 2) INDICATE CONNECTOR AT JOINT 2 OF
 TRUSS GT13 CAPABLE OF RESISTING 3121# OF
 UPLIFT.
  
 3) THE UPLIFT AT JOINT 16 OF TRUSS T14
 (1007#) EXCEEDS THE CAACITY OF THE
 SPECIFIED ANCHOR.
  
 4) NO ANCHORS WERE SPECIFIED ON THE PLAN
 FOR 2 OF THE T16 TRUSSES AT JOINT 1
 (UPLIFT 1519#).
  
 5) NO ANCHOR WAS SPECIFIED FOR TRUSS T17
 AT JOINT 19 (1790#).
  
 6) THE CAPACITIES OF THE ANCHORS
 SPECIFIED FOR TRUSS GT20 ARE EXCEEDED.
 TWO TAPR216 (1485# EACH) DERATED DUE TO
 PROXIMITY WOULD HAVE A CAPACITY OF LESS
 THAN DOUBLE AND UPLIFT AT JOINT 12 OF
 GT20 IS (4630#).
  
 7) THE UPLIFT VALUE OF 2 TAPR216 LOCATED
 IN CLOSE PROXIMITY WILL HAVE TO BE
 VERIFIED BY THE MANUFACTURER. TRUSS GT26
 AT JOINT 1 HAS UPLIFT OF 2488# AND
 (2) TAPR216 (1484# EA.) ANCHORS ARE
 SPECIFIED.
  
 NOTE: SEMCO AND HUGHES HAVE BEEN
 PURCHASED BY USP. SOME OF THE CONNECTOR
 CAPACITIES HAVE BEEN REDUCED AND OTHERS
 HAVE BEEN DISCONTINUED. PLEASE REFER TO
 THE LATEST USP CATALOG FOR TRUSS
 CONNECTOR INFORMATION.
  