Plan Review Notes
Plan Review Notes For Permit 01091712
Permit Number 01091712
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-02 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE A1.0 TOILET ROOM. PLEASE SUBMIT
 DETAILS TO SHOW COMPLIANCE WITH FACBC-97
 SEC. 4.22. SHOW CLEAR FLOOR SPACE SEC
 4.22.3, W/C TO BE 1'6" OFF WALL, LAV TO
 BE 1'3" OFF WALL. SHOWER TO COMPLY WITH
 SEC 4.21 PLEASE SHOW DETAILS.
 2) PAGE A1.0 & PAGE P-1. FLOOR DRAIN
 REQUIRED IN TOILET ROOM AND SHALL BE
 EQUIPPED WITH A TRAP PRIMER. SPC SEC
 409.4.1.1
 3) PAGE P-2 GENERAL NOTES #16. AIR
 CHAMBERS SHALL COMPLY WITH SPC 607.8.3
 AND BE RECHARGEABLE AND ACCESSIBLE. ALSO
 THEY ARE A "QUICK FIX" AND WATER HAMMER
 ARRESTORS SHOULD BE USED. THEY SHALL BE
 SIZED AND LOCATED PER MANU. INSTALL. IN-
 STRUCTIONS AND WH-PDI 201, CLOSE TO FIX-
 TURE.
 4) PAGE P-1 KEYNOTES #'S 12 & 13. SEPAR-
 ATE PERMIT REQUIRED FOR GAS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377