| Plan Review Notes For Permit 01091712 |
| Permit Number |
01091712 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-02 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE A1.0 TOILET ROOM. PLEASE SUBMIT | | | DETAILS TO SHOW COMPLIANCE WITH FACBC-97 | | | SEC. 4.22. SHOW CLEAR FLOOR SPACE SEC | | | 4.22.3, W/C TO BE 1'6" OFF WALL, LAV TO | | | BE 1'3" OFF WALL. SHOWER TO COMPLY WITH | | | SEC 4.21 PLEASE SHOW DETAILS. | | | 2) PAGE A1.0 & PAGE P-1. FLOOR DRAIN | | | REQUIRED IN TOILET ROOM AND SHALL BE | | | EQUIPPED WITH A TRAP PRIMER. SPC SEC | | | 409.4.1.1 | | | 3) PAGE P-2 GENERAL NOTES #16. AIR | | | CHAMBERS SHALL COMPLY WITH SPC 607.8.3 | | | AND BE RECHARGEABLE AND ACCESSIBLE. ALSO | | | THEY ARE A "QUICK FIX" AND WATER HAMMER | | | ARRESTORS SHOULD BE USED. THEY SHALL BE | | | SIZED AND LOCATED PER MANU. INSTALL. IN- | | | STRUCTIONS AND WH-PDI 201, CLOSE TO FIX- | | | TURE. | | | 4) PAGE P-1 KEYNOTES #'S 12 & 13. SEPAR- | | | ATE PERMIT REQUIRED FOR GAS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|