| 2001-12-21 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE AO. NEED THE ELEVATION |
| | CERTIFICATE. |
| | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH |
| | STRUCTURE AS RECOMMENDED ON THE PRE- |
| | LIMINARY SOIL TEST REPORT. |
| | 3-PRODUCT APPROVAL FOR SINGLE HUNG |
| | WINDOWS EXPIRED. |
| | -PROVIDE PRODUCT APPROVAL FOR FRENCH |
| | DOOR WITH SIDELITES IF OPTION SELECTED |
| | 4-MASTER BEDROOM CAN'T HAVE OPTION OF |
| | DOORS AT REAR ELEVATION BECAUSE IT |
| | WILL NOT COMPLY WITH TABLE 600 SBC/97. |
| | ONLY SIDE DOOR OPTION WILL COMPLY. |
| | 5-PROVIDE COMPLETE INFORMATION FOR STORM |
| | PANELS UNDER A SEPARATE PERMIT. |
| | 6-TRUSS DRAWINGS: |
| | -UPDATE ALL GENERAL TRUSS DETAILS. USE |
| | ASCE 7-95 FOR 140MPH, NOT ASCE 7-93. |
| | SEE COMMENTS ON TRUSSES. |
| | -DESIGNER OF RECORD TO REVIEW ALL TRUSS |
| | DRAWINGS AND CLEARLY INDICATE WHO |
| | REVIEW THE TRUSSES. (NAME OF FIRM). |
| | 7-PROVIDE MANUFACTURER'S CERTIFICATION |
| | FOR 2 HR FIRE RATED CONCRETE BLOCK |
| | ACCORDING TO THE EQUIVALENT THICKNESS |
| | AND AGGREGATES USED. SEE SECTION 709.3 |
| | SBC 1997. |
| | |
| | NOTES: |
| | -DRAWINGS AND COMMENTS TO BE FILED UNDER |
| | PERMIT #01091691. |
| | -THESE COMMENTS APPLY TO PERMIT #S: |
| | 01091691, 01091695, 01091697, 01091699 |
| | 01091701 AND 01091706. |