| Plan Review Notes For Permit 01091691 |
| Permit Number |
01091691 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-20 00:00:00 | DENIED | | | REFERENCE: SPC -94-FACBC-97 | | | | | | 1) PAGES 1, 1A, & 1B. MODEL 1527(L)(R). | | | M/BATH W/C TO BE 1'6" NOT 1'7" AS SHOWN | | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | | 2) SHOW CLEAR FLOOR SPACE FOR LAV AND | | | W/C IN 2ND BATH. | | | 3) PAGES 1, 1A, & 1B. MODEL 1409(L)(R). | | | M/BATH W/C TO BE 1'6" NOT 1'7" AS SHOWN. | | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | | 4) 2ND BATH MINIMUM OPENING FOR W/C IS | | | 2'9" NOT 2'8" AS SHOWN. ALSO SHOW CLEAR | | | FLOOR SPACE FOR LAV AND W/C. | | | 5) PAGES 1, 1A, & 1B. MODEL 1357(L)(R). | | | M/BATH W/C TO BE 1'6" NOT 1'7" AS SHOWN. | | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | | 6) 2ND SHOW CLEAR FLOOR SPACE FOR W/C & | | | LAV. | | | 7) PAGE 2, MODELS 1409(L)(R) & MODEL | | | 1527(L)(R) OPTIONAL LAUNDRY TRAYS NOT | | | VENTED PROPERLY. PLEASE RESUBMIT RISER | | | WITH PROPER VENTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|