2002-02-22 00:00:00TRUSSES DENIED
  
 1) THE DESIGN CRITERIA LISTED ON THE
 TRUSS DRAWINGS MUST BE ASCE7-95 TO
 COMPLY WITH THE 1997 SBC. NOTE: THE CITY
 OF WEST PALM BEACH IS LOCATED IN THE
 140MPH WIND ZONE ON THE ASCE MAP. THE
 TRUSS LAYOUT, THE TRUSS DRAWING COVER
 SHEET AND THE TRUSS DRAWINGS MUST ALL
 LIST THE SAME WIND LOAD DESIGN CRITERIA.
 PLEASE CORRECT.
  
 2) PROVIDE A LETTER FROM THE DESIGNER OF
 RECORD FOR THE STRUCTURE INDICATING A
 CONNECTOR THAT IS CAPABLE OF RESISTING
 THE LOADS AT JOINT 1 OF TRUSS TG1. THE
 UPLIFT GIVEN ON THE TRUSS DRAWINGS IS
 4470# AND A TA-5 RATED FOR 2490# IS
 INDICATED ON THE PLANS. NOTE: THE LETTER
 MUST BE SIGNED,SEALED AND DATED BY THE
 DESIGN PROFESSIONAL.
  